Step 6. Prepare The Backup Gateway For Mounting - Tesla Powerwall 2 AC Installation Manual

Backup gateway
Hide thumbs Also See for Powerwall 2 AC:
Table of Contents

Advertisement

Step 6. Prepare the Backup Gateway for Mounting

1. Remove the Backup Gateway from its packaging and verify that the contents are complete
and undamaged (see "Backup Gateway Box Contents," above).
2. Record the serial number of the Backup Gateway in the back of the Owner's Manual that
came with the system. The serial number can be found on a label on the inside of the
enclosure door, and also on the outside of its packaging.
3. Open the Backup Gateway enclosure and remove the enclosure door.
4. Remove the screw at the bottom of the dead front panel and remove it from the enclosure.
Figure 24: Removing the Dead Front Panel from the Enclosure
5. Determine whether cable entry to the Backup Gateway will be from the top, bottom, or side
of the enclosure. If cable entry will be from the top, skip to Step 7, "Install a Circuit Breaker in
the Backup Gateway."
6. To configure the Backup Gateway for cable entry from the bottom or sides, do the
following:
Remove the four fasteners holding the back panel assembly in place and remove it
from the enclosure.
Rotate the back panel assembly 180 degrees and reinstall it in the enclosure.
25

Advertisement

Table of Contents
loading

Table of Contents