Download  Print this page

Advertisement

100 V, 120 V, 200 V, 220 V, 230 V, 240 V Single-Phase Service
Main/Sub Panel Breaker Terminal
Line 1
Neutral
NOTE: For single-phase service, Neutral is not connected to the Powerwall N terminal. It is
instead connected to the Powerwall L2 terminal.
Main/Sub Panel Breaker Terminal
Line 1
Neutral
Line 2
Main/Sub Panel Breaker Terminal
Line 1
Line 2
4. On the Powerwall side, strip the ends of the wires and attach them to the corresponding
leads on the 3-pin AC power harness using the provided wirenuts.
5. Plug the AC power harness into the AC connector in the Powerwall wiring compartment.
Ensure that the connector clicks into place.
Figure 39: Powerwall 2 AC Power Harness Connection
NOTE: The Powerwall connection to the main electrical panel requires a 30 A circuit breaker
with a maximum short circuit current rating of 10 kA. This breaker serves as the disconnect for
the Powerwall, and must be wired in accordance with local wiring codes and regulations.
36
Powerwall Terminal
L1
L2
120/240 V Split-Phase Service
Powerwall Terminal
L1
N
L2
208 V Service
Powerwall Terminal
L1
L2
Wire Gauge
5–8 mm
2
(10-8 AWG)
5–8 mm
2
(10-8 AWG)
Wire Gauge
5–8 mm
2
(10-8 AWG)
5–8 mm
2
(10-8 AWG)
5–8 mm
2
(10-8 AWG)
Wire Gauge
5–8 mm
2
(10-8 AWG)
5–8 mm
2
(10-8 AWG)
Powerwall Installation Manual

Advertisement

Table of Contents

   Also See for Tesla Powerwall 2 AC

   Related Manuals for Tesla Powerwall 2 AC

Comments to this Manuals

Symbols: 0