ELECTRICAL CONNECTIONS
All works concerned with electrical installation must be carried out by a skilled and
qualified personnel.
Make sure that all incoming power supplies are isolated before installation and
maintenance of the ElectroVap MC2 humidifier.
A)
2 x 220-230V
Q2: 2 poles
220 V /
L
230V
N
50-60Hz
Q1 and Q2: MCB and electrical power isolation
C) 3 phases + neutral: 3 x 380-400 V
Q2: 4 poles
3x380V
3x400V
50-60Hz
+ neutral
N
Nota: for connecting optional ventilation pack or humidistat, please refer to pages n°21 & 40
of this manual.
Failure to observe manufacturer's installation recommendations will invalidate the manu-
facturer's warranty.
ALL WORKS CONCERNED WITH ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A SKILLED AND QUALIFIED PERSONNEL
E
LECTRO
Installation - Step 5
1 - Power supply isolator and MCB ( near the unit )
2 - Power supply cable
1
3– Electrical compartment
3
WARNING :
Failure to fit an electrical power isolator and MCB as
part of the electrical installation significantly increases
2
the risk of electric shock, which can be fatal.
ELMC 5
L1
L2
L3
N
L
PE
ELMC
5/3 to 90
L1
L2
L3
N
L
PE
V
MC2
AP
B) 3 X 380-400 V without neutral
Q2: 3 poles
3 x 380V /
3 x 400V
50-60Hz
220-230V
50-60Hz
Q1: 2 poles
The symbol ∆ between Q1 & Q2 means that
these MCB are coupled. The power MCB Q2
and control MCB Q1 are mechanically linked
together. So if a fault is detected, the power and
the control circuits are switched off and there is
no voltage on the unit. The unit is really off
voltage.
D) 3 phases without neutral: 3 x 380-400 V
In this case, a transformer (option) must be ins-
talled (See technical notice page n°33)
31
ELMC 5
to 90
L1
L2
L3
N
L
PE
2A
Pictures for illustrating purposes only