It is recommended that the ElectroVap RTH humidifier be kept in its transit packaging for as long as possible prior to maintenance. If the humidifier is to be put into storage prior to installation, it must be stored under cover and protected from physical damage, dust, frost, rain and humidity.
This section should be read carefully to ensure safe and correct installation of your humidifier. GENERAL This manual contains all details necessary for the planning and installation of the ElectroVap RTH humidifier. In addition commissioning and maintenance details are included.
Page 6
RTH-V2 LECTRO Dimensions Face Front Face Front Side Côté RTH-V2 5 to 50 RTH-V2 60 to 100 A Width 1200 B Height C Depth D Steam outlet 1 E Steam outlet - Side view F Tank draining - Front view G Tank draining - Side view H Entrée d’eau - Face Water inlet - Side view...
Page 7
RTH-V2 LECTRO Unit wall installation Unpack the unit and check for any dama- ge. A drilling template is supplied with the packing : make sure to pick it up before throwing away the packing ma- terial. Damage to packing and/or unit must be noticed to carrier by registered letter wi- thin 3 working days.
Page 8
RTH-V2 LECTRO Unit wall installation (continued) Unlock the tank cap and lay it upside down on the top ceiling of the humidifier. Release the holding steel cord while holding the tank; Let the tank gently tip under it stops; Insert screws on 4, 5, 6 & 7 and thighten up all the 7 (RTH 5 to 50) or 11 (RTH 60 to 100) screws.
Page 9
RTH-V2 LECTRO Unit wall installation (continued) RTH 60 to 100 52,7 44,5 11 x Ø 8.5 mm holes 11 trous O 8,5mm For a ground installation, support legs are available (s.a. attached pictures) : - Part nb : 999995 for RTH 5 to 50 - Part nb : 999993 for RTH 60 to 100 ref: 999995 ref: 999993...
RTH-V2 LECTRO Water connection A fresh mains cold water service should be used to supply the unit. The water pressure should be between 1 & 6 bars & should not exceed 40°C in temperature. The water supply connection is under the bottom of the unit. The humidifier is delivered with a water inlet hose of 50 cm long with a 3/4"...
RTH-V2 LECTRO Steam output 1. Use preferably hose from our supply NB : when brand new hoses are installed, a smell of burning may be smelt during the first running of the steam humidifier. This is normal and will eventually dispel. 2.
Condensate draining The following drawings show the water draining connections that should be made. 1. The devatec supplied steam hose should be used : Fig.1 RTH 5 to 100 : 1.5 m Ø 40mm hose with 1 hose clamp (supplied).
RTH-V2 LECTRO Condensate draining Drain water cooling kit (option) How it works The draining water of a steam humidifier is very hot and it may be necessary to cool it down. This unsophisticated device makes it possible to cool it down to 65°C (149°F) when the fee- ding water is around 15°C (59°F).
(absorbing distances) as short as 600 mm. devatec For further reference, please contact or their authorized agent. ExpressPack Steam distribution selection table Steam distribution Steam distribution...
Page 15
RTH-V2 LECTRO Steam pipe positioning POSITIONING OF THE STEAM DISTRIBUTI0N PIPE Evaporation distance or vapor trail « D » A certain length is required so that the steam coming out of the steam distribution pipe be absorbed by the air. All along this length, descrided as the evaporation distance, the steam can still be seen in the airflow as a mist which can condensate in water against any obstacle if placed within.
Page 16
A high humidity limit humidistat must be installed in the duct to stop the humidifier in case the level of humidity exceeds the preset value. In case the recommended distances cannot be met, please contact devatec or their authorized agent for an alternative solution.
Page 17
Steam pipe positioning Please meet the following dimensions and spaces according to your configuration. For further information, please contact devatec or their authorized agent. H1 = 110mm = Minimum height between the duct floor and the axle of the steam pipe.
Page 18
RTH-V2 LECTRO Steam pipe positioning (continued) In duct with limited height, the distribution pipe(s) can be tilted In vertical ducts where the air flow is upward by 30 ° to get the 80 mm minimum height. or downward, the steam distribution pipe(s) must be tilted by 15°...
Page 19
RTH-V2 LECTRO Steam pipe installation For ensuring the best steam distribution possible, we would recommend to install the steam pipes in either diameter as per the two methods described underneath. How to install in a duct Your steam pipes must be screwed onto the ventilation duct by the fixing plate with a set of 4 bolts and nuts of Ø 5 mm.
Page 20
As far as the EHF-3 is concerned, please revert to the recommendations given on the EHF-3 information sheet. Never connect the EHF-3 unit on the terminals 3 & 4 of the humidifier when a 100VA transformer is installed inside the ElectroVap RTH Examples of installation humidifier.
Page 21
RTH-V2 LECTRO Electrical installation Recommandations: All works concerned with the electrical installation must be carried out by skilled and qualified personnel (eg electrician with appropriate training). The customer is responsible for ensuring their suitability. Please observe local regulations concerning the provision of electrical installations. Check all electrical terminal screws at commissioning, after 50 hours operation and at every service thereafter.
Page 22
RTH-V2 LECTRO Electrical tables RTH steam humidifier in 1 x 115V - 50/60Hz Steam Nb of Power of Nb of Amperage Power Nb of production Voltage (V) heating heating element phase(s) (KW) boiler(s) (kg/h) element(s) (KW) 4,3 (230V) 4,3 (230V) 13,5 1,9 (230v) RTH steam humidifier in 1 x 230V - 50/60Hz...
Page 23
RTH-V2 LECTRO Electrical table RTH steam humidifier in 3 x 208V - 50/60Hz Steam Nb of Power of Nb of Amperage Power Nb of production Voltage (V) heating heating element phase(s) (KW) boiler(s) (kg/h) element(s) (KW) 1,9 (230V) 4,3 (230V) 3 x 1,9 (230V) 3 x 4,3 (230V) 4,3 (230V)
Page 24
RTH-V2 LECTRO Electrical table RTH steam humidifier in 3 x 380V - 50/60Hz Steam Nb of Power of Nb of Amperage Power Nb of production Voltage (V) heating heating element phase(s) (KW) boiler(s) (kg/h) element(s) (KW) 1,9 (277V) 1,9 (230V) 4,3 (277V) 4,3 (230V) 4,3 (277V)
Page 25
RTH-V2 LECTRO Electrical table RTH steam humidifier in 3 x 415V - 50/60Hz Steam Nb of Power of Nb of Amperage Power Nb of production Voltage (V) heating heating element phase(s) (KW) boiler(s) (kg/h) element(s) (KW) 1,9 (277V) 1,9 (230V) 4,3 (277V) 4,3 (230V) 4,3 (277V)
Page 26
RTH-V2 LECTRO Electrical table RTH steam humidifier in 3 x 460V - 50/60Hz Steam Nb of Power of Nb of Amperage Power Nb of production Voltage (V) heating heating element phase(s) (KW) boiler(s) (kg/h) element(s) (KW) 1,9 (277V) 4,3 (277V) 3 x 1,9 (277V) 3 x 4,3 (277V) 4,3 (277V)
Page 27
RTH-V2 LECTRO Electrical table RTH steam humidifier in 3 x 575V - 50/60Hz Steam Nb of Power of Nb of Amperage Puissance Nb of production Voltage (V) heating heating element phase(s) (KW) boiler(s) (kg/h) element(s) (KW) 1,9 (346V) 4,3 (346V) 3 x 1,9 (346V) 3 x 4,3 (346V) 4,3 (346V)
Page 28
RTH-V2 LECTRO Wiring connections RTH 5 External protection External POWER power In the e lectrical installation, an protection all pole sw itch w ith a m inim um contact w id th of 3 m m m ust be provided 2 A external power COMMAND...
Page 29
RTH-V2 LECTRO Wiring connection (CONTINUED) Humidifier without neutral fitted with a 400/230V transformer The RTH 7 to 100 humidifiers are electrically supplied in 3x400v + G + N. In case a neutral line is not available, this can however be easily substitued by the use of our optional transfomer preventing the installation of a specific neutral line.
RTH with humidity sensor 2-10V 4-20V signal signal signal signal High level safety humidistat V+ GND RH Devatec sensor or jumper Alim +15Vdc A 24Vac (2VA) supply is Dip-switch S1 available 1 2 3 4 1 2 3 4 0-5V sensor Devatec...
RTH-V2 LECTRO Connecting options The wiring of the optional equipment described under must be made with 0.75 mm2 flexible cable. REMOTE INFORMATION BOARD (OPTION) Contact can be modified in NO or NF by wiring as per the following schemes (ex: wiring on 30 & 31 = NO contact). 30 31 32 33 34 35 36 37 38...
Page 32
RTH-V2 LECTRO Connecting options RS485 OR RS422 OR RS232 CIRCUIT BOARD (OPTION) SPECIFICATIONS RS485 : 2 wires half duplex (+GND) Maximum length : 1200 m. RS422 : 4 wires half duplex (+GND) On demand—Max length 1200 RS232 : 2 wires half duplex (+GND) On demand—Max length : 20 m. Bias : 620 Ohms pull-up and pull-down (jumper selectable) Termination : 120 Ohm (jumper selectable) Protocol : JBUS or MODBUS (asynchronous of 8 bit data, no parity...
RTH-V2 LECTRO Connecting options RS485 or RS422 or RS232 interface protocol : Pictures for illustrating purposes only ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
Page 39
RTH-V2 LECTRO Wiring diagrams RTH 5 & 8 STEAM HUMIDIFIERS in 1 x 230V Butée Butée 2/T1 3/A1+ 1/L1 4/A2- Butée 14NO 13NO COUVERCLE VUE DE DESSUS Façade appareil / Butée Front Unit 4,3KW-230V 4,3KW-230V 1,9KW-230V Pictures for illustrating purposes only ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
Page 44
RTH-V2 LECTRO Wiring diagrams RTH 60 & 70 STEAM HUMIDIFIERS in 3 x 380 - 400V - 415V Left tank (cuve gauche) 2/T1 3/A1+ 1/L1 4/A2- 2/T1 3/A1+ Right tank (cuve Droit) 1/L1 4/A2- 2/T1 3/A1+ 1/L1 4/A2- 2/T1 3/A1+ Façade Façade appareil /...
Page 45
RTH-V2 LECTRO Wiring diagrams 80 STEAM HUMIDIFIER in 3 x 380 - 400V - 415V Left tank (cuve gauche) 2/T1 3/A1+ 1/L1 4/A2- Right tank (cuve Droit) 2/T1 3/A1+ 1/L1 4/A2- 2/T1 3/A1+ Façade Façade 1/L1 4/A2- appareil / appareil / Front Unit Front Unit 2/T1...
Page 46
RTH-V2 LECTRO Wiring diagrams RTH 90 & 1 00 STEAM HUMIDIFIERS in 3 x 380 - 400V- 415V 37 28 Left tank (cuve gauche) 2/T1 3/A1+ 1/L1 4/A2- Right tank (cuve Droit) 2/T1 3/A1+ 4/A2- 1/L1 2/T1 3/A1+ 1/L1 4/A2- Façade Façade appareil /...
Page 47
RTH-V2 LECTRO Wiring diagrams WATER LEVEL MANAGEMENT BOARD RTH WITH 1 OR 2 CONTACT0RS S1, S2 RTH WITH 3 OR 4 CONTACTORS S1, S2, S3, S4 Connecting the water level sensor WATER LEVEL SENSOR Pictures for illustrating purposes only ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
RTH-V2 LECTRO Setting up Before putting your humidifier in operation, please make sure that your installation be in conformity with the manufacturer’s technical specifications. Open the water valve of the main water line. Switch on the main power supply contactors (voltage and command).
Page 49
RTH-V2 LECTRO User menu information TTENTION A press on button 1 will allow you to shift to sub-menu for changing configuration parameters. Then scroll display using the up (2) or down (3) keys. The selected parameter will flash and press return key (1) for recording. STARING UP HUMIDIFIER STATUS SOFTWARE VERSION...
Page 50
RTH-V2 LECTRO User menu information (CONTINUED) - Press the key for changing menu at any time. WATER TEMP IN TANK This shows the temperature inside the tank ….°C This show in kg what left in steam PRODUCT BEFORE production before maintenance. This CLEAN ….
Page 51
RTH-V2 LECTRO Humidifier status menu TTENTION A press on button 1 will allow you to shift to sub-menu for changing configuration parameters. Then scroll display using the up (2) or down (3) keys. The selected parameter will flash and press return key (1) for recording. HUMIDIFIER CONFIGURATION CONTROL SIGNAL IN...
RTH-V2 LECTRO Changing parameters menu How to change the operating parameters / Example: STEAM CAPACITY LIMIT : .…%. Scroll menu to get this message, press the key and the value will flash. Using the keys, increase or decrease the value. Once the desired value is reached, press the key to enter the data.
RTH-V2 LECTRO Changing parameters menu (continued) MAINTENANCE INTERVAL This is to adjust the estimated …..H working time before This is to keep or not the water SETTING WATER T°C temperature at 65°C when the °C YES / NO humidifier is on halt This is to adjust the temperature MINIMUM T°C OF maintained inside the tank when the...
RTH-V2 LECTRO Alerts and Warnings Alerts What you should do when : NO WATER IN THE WATER Humidifier status : the unit is on halt LEVEL DETECTOR Switch the humidifier off. Control the internal water piping. Please revert to the « maintenance » section of this manual Control the water level detection system.
Page 55
RTH-V2 LECTRO RTH 5 to 50 tank maintenance RTH 5 to 50 Picture n°1 Drain the tank out by pressing the manual drain button (s.a. picture n°1). Wait for com- plete draining and allow the tank to cool down (if this feature has been enabled). Cut off the power supply at the power switch- board and switch off the RTH humidifier.
Page 56
RTH-V2 LECTRO RTH 5 to 50 tank maintenance (continued) Lift the tank lid (mind the positioning marks) and lay it upside down on the top of the humidifier Picture n°7 (s.a. picture n°7). Remove the high water tank and lay it on the top of the humidifier. Set the calcius collecting bag on the tank rim and hook the handles to the tank lateral hooks (s.a.
Page 57
RTH-V2 LECTRO RTH 60 to 100 tank maintenance RTH 60 to 100 Picture n°13 Drain both tanks by pressing the drain but- ton (s.a. picture n°13) and wait for their complete draining and cooling (if this op- tion has been enabled). Cut the mains off (from the general power switchboard) and switch off the humidifier (s.a.
Page 58
RTH-V2 LECTRO RTH 60 to 100 tank maintenance (continued) Picture n°18 Make the drain valve assy slide on the right and the other drain hose butt end to the left (s.a. picture n°18). Picture n°19 Plug off the drain valve electrical supply wires and take off the drain valve assy (s.a.
Page 59
RTH-V2 LECTRO RTH 60 to 100 tank maintenance (continued) Picture n°24 Take off the collecting container and swing back the tank in intermediate position. Fasten the tank holding steel cord. TAKE CARE : the tank gasket should be changed whenever the tank is maintained (picture n°24.1). Make also sure that the collar clamps are still ok.
RTH-V2 LECTRO Valve maintenance Drain valve maintenance To be made a each tank maintenance : Remove screw 1 then swing coil holder 2 on the left. Remove coil 3 from the actuator assembly 4 (don’t miss the small parts). Dismount assembly 5, clean valve 6 and rinse body 7.
Page 61
RTH-V2 LECTRO Split view & component parts Overview : RTH-V2 5 to 50 Pictures for illustrating purposes only...
Page 62
RTH-V2 LECTRO Split view & component parts Overview : RTH-V2 60 to 100 Pictures for illustrating purposes only...
Page 63
RTH-V2 LECTRO Split view & component parts Stainless steel tank RTH-V2 5 to 50 Part Description Stainless steel tank + lid 930500 Heating element 1,9 kW (230V) 930547 Heating element 1,9 kW (277V) 930543 Heating element 1,9 kW (346V) 930503 Heating element 4,3 kW (230V) 930548 Heating element 4,3 kW (277V)
Page 64
RTH-V2 LECTRO Split view & components parts Stainless steel tank (left) RTH-V2 60 to 100 Part Description Chaudière inox + couvercle 930500 Heating element 1,9 kW (230V) 930547 Heating element 1,9 kW (277V) 930543 Heating element 1,9 kW (346V) 930503 Heating element 4,3 kW (230V) 930548 Heating element 4,3 kW (277V)
Page 65
RTH-V2 LECTRO Split view & components parts Stainless steel tank (right) RTH-V2 60 to 100 Part Description Stainless steel tank + lid 930500 Heating element 1,9 kW (230V) 930547 Heating element 1,9 kW (277V) 930543 Heating element 1,9 kW (346V) 930503 Heating element 4,3 kW (230V) 930548...
Page 66
RTH-V2 LECTRO Split view & components parts Filling cup RTH-V2 5 to 50 Part nb Description 930518 Water hose hose Ø18x22mm - L. 93cm 930082 Tightening clamp Ø16x27mm 930520 Overflow hose Ø18x22mm - Lg103cm 930517 Water feeding hose Ø12x16mm - Lg31,5cm 930231 Filling cup + lid 930081...
Page 67
RTH-V2 LECTRO Split view & components parts Water level detection tank RTH-V2 5 to 100 Part nb Description 930521 Water level sensor (set of 4 electrodes) Stainless steel nut Ø4mm " Flutted chromium platted tip 1/4 G - Ø8mm 930523 Black O ring SIL70 (bag of 2) 930522 RTH-V2 water level tank...
Page 68
RTH-V2 LECTRO Split view & components parts Drain valve RTH-V2 5 to 50 Part nb Description Ø40mm - L.80mm steam hose Ø40X60mm tightening clamp 930512 Membrane bellows for D137 930509 Core assy + spring for D137 930510 230V - 30W drain coil for D137 930511 Core guide assy for D137 930508...
Page 69
RTH-V2 LECTRO Split view & components parts Water inlet valve RTH-V2 5 to 50 Part nb Description 930160 Water inlet valve coil Water inlet valve body N2 930224 " nut 930151 Water inlet valve Water inlet valve RTH-V2 60 to 100 Part nb Description 930160...
Page 70
RTH-V2 LECTRO Split view & components parts Electrical components RTH-V2 5 to 100 Part nb Description 930530 Water level control board (ref: 500851/02) 930532 RTH main board (ref: 500101/05) 930106 Remote information board (option) (ref: 500400/03) 930101 Display board (réf: 500600/03) Ø4 - Lg8mm stainless steel cylindrical head screw Ø4 - Lg60mm stainless steel cylindrical head screw Ø4mm stainless steel plain washer...
Page 71
Pictures for illustrating purposes only...
Page 72
Export Division: tel. +33 (0)2 35 83 06 44 ou +33 (0)2 35 83 03 86 fax. +33 (0)2 35 85 36 72 LR 94104-2 Email: export@devatec.com - www.devatec.com Pictures for illustrating purposes only devatec reserves the right to change specifications or design of the equipment described in this brochure without prior notice.