Devatec ELMC 5 Manual

Devatec ELMC 5 Manual

Steam humidifier
Hide thumbs Also See for ELMC 5:

Advertisement

Steam humidifier
Humidificateur vapeur
ELMC tech. rev.6.1 20-02-2008

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ELMC 5 and is the answer not in the manual?

Questions and answers

Summary of Contents for Devatec ELMC 5

  • Page 1 Steam humidifier Humidificateur vapeur ELMC tech. rev.6.1 20-02-2008...
  • Page 2: Table Of Contents

    ElectroVap MC Contents Safety information Declaration of conformity INSTALLATION Unit mounting Water connection Dimensions Steam outlet Condensate draining Ventilation units Steam distribution pipes Steam pipes positioning Calculation of evaporation distance Optional temperature control system ELECTRICAL INSTALLATION Outlet wiring diagram Steam capacity Electrical features Electrical and control connections 19-21...
  • Page 3: Safety Information

    ElectroVap MC Safety information Important This section should be read carefully to ensure the safe and correct installation of your humidifier GENERAL This manual contains all details necessary for the planning and installation of the ElectroVap MC humidifier. In addition commissioning and maintenance details are included. The manual is intended for use by engineers and properly trained technical personnel.
  • Page 4: Declaration Of Conformity

    Low Voltage Directive 73/23/EEC Standard(s) to which EN50081-1: 1992, EN50082-1: 1992 Conformity Is declared: EN349: 1993 EN60204-1: 1993, EN292 Parts 1&2: 1991 Manufacturer’s Name and Address DEVATEC Rue Saint Eloi 76550 Ambrumesnil - FRANCE Authorised Representative Type of equipment ELECTROVAP MC Model Name (s) &...
  • Page 6: Unit Mounting

    ElectroVap MC Unit wall installation Unit mounting Unpack the ELMC humidifier and check for any damage. Damage to packing and/or unit must be reported by registered letter to carrier within 3 working days. Provide free space all around the unit : 1 m. to 1.20 m. (3 to 3 ft.) from the floor to the bottom of the humidifier, 1.25 m.
  • Page 7: Water Connection

    The water supply must be made without any additional chemicals (chlorine, disinfectant, ozone). Also some water qualities may generate foam causing disturbances with the correct control of the humidifier. Please refer to Devatec technical services for further assistance.
  • Page 8: Dimensions

    ElectroVap MC DIMENSIONS Unit mounting LMC 5-8-10 Dimensions Steam Steam Weight Weight outlet drain empty kg full kg ø LMC 15-20-30 Dimension Steam Steam Weight Weight outlet drain empty kg full kg ø LMC 40-50-60 Dimension Steam Steam Weight Weight outlet drain empty kg full kg...
  • Page 9: Steam Outlet

    ø 25 mm = 250 mm (minimal) ø 40 mm = 400 mm (minimal) Number of steam outlet ELMC 5-8-10-15 = 1 x ø 25 mm ELMC 20-30 = 1 x ø 40 mm ELMC 40-50-60 = 2 x ø 40 mm ELMC 90 = 3 x ø...
  • Page 10: Condensate Draining

    The following drawings show the water draining connections that should be made. Connection to the unit by a hose draining diam25 ELMC 5-30: 1 m hose with 3 hose clamps ELMC 40-60: 1m+1.20m hose with 6 hose clamps. ELMC 90: 1m+1.20m+1.80m hose with 9 hose clamps Please follow the recommendations hereafter.
  • Page 11: Ventilation Units

    3 and 4 on the DIN rail (230V, 2 cores+ground). 15° Egout Model CVMC 1 CV 2 Egout Model Weight Db Max steam M3/H Compatible KG/ST/H with model CVMC 1 150 ELMC 5/8/10 CV 2 ELMC 15/20...
  • Page 12: Steam Distribution Pipes

    ElectroVap MC Steam distribution pipe Installation Steam from the cylinder enters the duct via a steam distribution pipe. In order to obtain optimum performance of the humidifier, it is recommended that these instructions are adhered to as far as possible. steam distribution pipe selection This table shows the number and the diameter of...
  • Page 13: Steam Pipes Positioning

    ElectroVap MC Steam pipe positioning Installation Positioning the recommended template profile for cut-out in DUCT/AHU (at the end of the brochure) A minimum distance of 300mm between the center of the steam distribution pipe and the top of the duct should be allowed. Where the distribution pipe is installed at an angle of between 30°C and 45°C, this may be reducted to 150mm.
  • Page 14: Calculation Of Evaporation Distance

    ElectroVap MC Calculation of the evaporation distance Installation In order to determine the evaporation distance, the enclosed calculation table can be used with : RH1 = relative humidity of the air before humidification Before or after ventilation area RH2 = Relative humidity of the air after humidfication in % RH Max = maximum difference between RH1 &...
  • Page 15: Optional Temperature Control System

    ElectroVap MC Optional temperature control sys INSTALLATION For sanitation : this system holds the water in the cylinder at a temperature of 65°C (150°F) to prevent bacteria or mold from forming in the cylinder if there is no humidity demand. For fast boiling : when there is a demand for humidity, the water boils more quickly than with cold water.
  • Page 16: Electrical Installation

    ElectroVap MC Electrical installation All works concerned with the electrical installation must be carried out by skilled and qualified personnel (eg electrician with appropriate training). The customer is responsible for ensuring their suitability. Please observe local regulations concerning the provision of electrical installations. After about 50 hours of operation, all the screws of the power terminals must be retightened.
  • Page 17: Outlet Wiring Diagram

    (safety & room ventilation unit) (Terminal block 1-2). This allows the selection of the suitable regulation. Configure dip switch S1 as follows : Devatec sensor 0-10 V 0-10 V/2-10 V regulator 0-5 V sensor Red lamp of 1-5 V sensor...
  • Page 18: Steam Capacity

    ElectroVap MC Steam capacity Electrical installation The 2 tables under indicate the nominal value of the steam capacity in steam Kg per hour, the electrical power and the intensity according to the different power supplies. 2 x 230 V 3 x 230 V 3 x 400 V 3 x 415 V 3 x 440 V...
  • Page 19: Electrical Features

    ElectroVap MC Wiring Characteristics Electrical installation The below table indicates the electrical supply of the ElectroVap MC units. In all cases, the control circuit must be in single phase 230V. 2 x 230 V 3 x 230 V 3 x 400 V 3 x 415 V 3 x 440 V 50/60 Hz...
  • Page 20: Electrical And Control Connections

    Electrovap MC Electrical connections Electrical Installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 21: Electrical Connection

    ElectroVap MC Electrical Connection When neutral is not available Electrical installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 22 ElectroVap MC Electrical connections Electrical Installation Terminal blocs on the Din rail Connection onto the board Connection onto the board Connection onto the board All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 23: Wiring The Remote Information System

    ElectroVap MC Wiring cables for remote Information system Electrical installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 24: Master-Slave System

    ElectroVap MC The ELMC steam humidifiers can be run as a master and slave system. You have to connect the regulator signal on (Connector x5 terminals 18-19-20) and servo control (terminals 1-2) to a master unit ( ex: the closer to the regulation system ) and to send back this wiring on the other units (slaves).
  • Page 25 ElectroVap MC With a regulation 0– 20 V The wiring diagram is the same as that of a 0 – 10 V regulation. Only dip-switch S1 ( 0 – 20 V ) should be set on and the software ( code 2.3.4 ) "CHOICE REGULATION " adjusted for "REGULT 0 –...
  • Page 26: Elmc Wiring Diagrams

    ElectroVap MC ELMC 5-2 wiring diagram Electrical Installation Application date : 06-11-06 From unit S/N : 100120 Through the door Through the divider Through unit depth All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 27 ElectroVap MC ELMC 5-3 wiring diagram Electrical Installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 28 ElectroVap MC LMC 8-10-15-20 WIRING DIAGRAMS Electrical Installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 29 ElectroVap MC ELMC 30 wiring diagram Electrical Installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 30 ElectroVap MC ELMC 40 wiring diagram Electrical Installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 31 ElectroVap MC ELMC 50-60 wiring diagram Electrical Installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 32 ElectroVap MC ELMC 90 wiring diagram Electrical Installation All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
  • Page 33: Final Inspection

    Electrovap MC Final inspection prior to commissioning Installation General 1. Visualy inspect the entire installation for loose or unconnected cables and for any disconnected pipework. 2. Check the steam cylinders are located correctly in the drain valve. 3. Check electrode cable connections on the top of the steam cylinder/s.
  • Page 34: Final Inspection

    Electrovap MC Final inspection continued Installation Steam Distribution Hose/Pipe 1. Inspect the steam distribution pipe and ensure there are no horizontal runs. 2. If flexible steam hose is used check the overall length is less than 3m. 3. If copper pipe is used check the effective length is less than 6m..
  • Page 35: Front Panel Identification

    ElectroVap MC Front panel identification Software assistant Alpha digital display Changing program Scrolling program Scrolling program Manual draining Steam production light ON/OFF Switch Power light Identification tag...
  • Page 36: Elmc Commissioning

    ElectroVap MC ELMC commissioning Software assistant Checking and Switching on 1 - After completion of the installation inspection, switch on the water supply to the unit. 2 - Switch on the main power supply. 3 - The power lamp must be illuminated. 4 - Switch on the main power supply I/0 on I.
  • Page 37: Menu User Information

    2 steps 3 steps 4 steps Indicates the Rh from the sensor in case Signal of the regulation in case with an of incorporated proportional + Devatec external regulation sensor STEAM DEMAND This shows the steam demand in the installation from 20 to 100 %.
  • Page 38: Menu User Information

    ElectroVap MC Menu user information Software assistant Roll up or down the menu in pushing on keys , press the select button to change menu. This indicates the steam production time PRODUCT BEFORE before maintenance – it allows to plan CLEAN KG/V the cleaning intervention...
  • Page 39: Menu Humidifier Condition

    This Indicates all possible control modes CONTROL SIGNAL IN that can be used: 0/10 V ON/OFF, 2-3-4 steps, proportional : (0-10V, 0-20V, 0-20mA, 1-5V, 2-10V, 4-20mA, Sensor (Devatec, 0-10V, 0-5V, TOTAL STEAM PROD. 4-20ma), slave regulation. TOTAL STEAM Total steam production since the commissioning...
  • Page 40: Menu Changing Parameter System

    ElectroVap MC Menu configuration changing Software assistant Scroll the menu up or down by pushing on keys , press the select button change menu. Menu : CHANGING UNIT CONFIGURATION With the humidifier switched on, press the DIAL ACCESS CODE key until the Change System Parameters menu is displayed.
  • Page 41 ElectroVap MC Menu configurations changing Software assistant Scroll the menu up or down by pushing on keys, press the select button to change menu. POWER OFF IF This allows to switch the contactor off when draining, avoiding current DRAINING leakage. This selects how unit responds to the ADJUSTMENT STEAM BY : Factory setting : Evaporation...
  • Page 42: Faults Messages

    ElectroVap MC ElectroVap MC ElectroVap MC Electrical features Electrical features Electrical features Software assistant P ALERTS TROUBLE CAUSES / ACTIONS OPTION Check power supply, fuses Power phase P0 ALERT A power phase is missing or power circuit breaker detection device is (general power switchboard) required F1 fuse (2A) or contactor...
  • Page 43: Maintenance Of The Cylinder

    ElectroVap MC Cylinder maintenance Maintenance The ElectroVap ELMC is delivered with disposable cylinder(s) in standard which can be replaced by cleanable ones, however, without any modification, according to the choice of the user. Drain the steam cylinder using the manual drain key. When the cylinder is fully drained switch off the unit and isolate the power.
  • Page 44: Cylinder Maintenance Guide

    The water quality is to be mentioned on your request so that to fit the most appropriate steam cylinder for the best working of the humidifier. Lenght of the genuine stainless steel electrodes : Model ELMC 5 ELMC 8-10 ELMC 10 single ph ELMC 15 to 90 Length (mm) During cylinder maintenance, it is recommended to measure the length of the electrodes.
  • Page 45: Maintenance Of The Valves

    ElectroVap MC Valves maintenance Maintenance Drain valve maintenance Drain the steam cylinder fully and remove it from the humidifier. Isolate power and water supply before To be made at each cylinder attempting to carry out any maintenance. maintenance • Remove the cap from, the end of the solenoid valve 1 •...
  • Page 46: Maintenance Sheet

    ElectroVap MC Follow up and maintenance file Model : ELMC Maintenance Model : ELMC INTERVENTION NEXT MAINTENANCE WORKS EFFECTED DATE INTERVENTION...
  • Page 47: Drilling Templates

    ElectroVap MC Drilling template...
  • Page 48 ElectroVap MC Drilling template...
  • Page 49: Drilling Templates

    ElectroVap MC Drilling template...
  • Page 50 +33 (0)2 35 83 06 44 Export division: or +33(0)2 35 83 03 86 fax. +33(0)2 35 85 36 72 - export@devatec.com ELMC tech Rev.6.1 - 20-02-08 edition devatec reserves the right to change specifications or design of the equipments described in this brochure...

Table of Contents