52
CMS-700 SYSTEM CIRCUIT MONITORING SYSTEMS (CMS)
—
Modbus
—
Communication to CMS
Physical Interface RS-485
To communicate with the CMS from an upper system, all devices (masters & slaves) must have the same
data rate and data format. These settings are defined over the Web UI, as described in the dedicated
chapter.
Parameter
Data rate
Data format
Line termination resistor (120Ω) needs to be added, if necessary, for CMS-700 having serial number
later than 700K1820000.
Control unit's MODBUS-ID
You can connect up to 247 control units to one Modbus RTU line. Each control unit must have a unique
Modbus ID (address).
Function Code
• Read operation on registers with access code "R" or "RW" is defined by function 03h "Read Holding
Registers"
• Write operation on registers with access code "W" or "RW" is defined by function 06h "Write Single
Register"
Do not apply functions other than those specified.
Values
2400, 4800, 9600, 19200, 38400, 57600, 115200 Bit/s
even parity, odd parity, without parity
Modbus RTU
Default Values
19200 Bit/s
even parity
CMS Systems