ABB CMS-700 User Manual page 64

Circuit monitoring system
Hide thumbs Also See for CMS-700:
Table of Contents

Advertisement

CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)
Modbus and SNMP Mapping
Addr.
Addr.
Word
Description
(hex)
(dec)
(16-bit)
Mains measurement registers
90B0
37'040
2
ACTIVE ENERGY L2 100Wh
90B2
37'042
2
ACTIVE ENERGY L3 100Wh
90B4
37'044
2
3-PHASE SYS. ACTIVE ENERGY 100Wh
90B6
37'046
2
REACTIVE ENERGY L1 100varh
90B8
37'048
2
REACTIVE ENERGY L2 100varh
90BA
37'050
2
REACTIVE ENERGY L3 100varh
90BC
37'052
2
3-PHASE SYS REACTIVE ENERGY 100varh 100
90BE
37'054
2
APPARENT ENERGY L1 100VAh
90C0
37'056
2
APPARENT ENERGY L2 100VAh
90C2
37'058
2
APPARENT ENERGY L3 100VAh
90C4
37'060
2
3-PHASE SYS. APPARENT
ENERGY 100VAh
9088
37'000
2
CURRENT THD L1
908A
37'002
2
CURRENT THD L2
908C
37'004
2
CURRENT THD L3
*) 96 group names with max. 64 characters can be defined in the Web-UI. The register contains the group name included in the group name list.
The register indicates the number of the group within the group name list.
**) The register indicates the number of the group in the group name list.
Resolution
Unit
Format
(1-bit value)
100
Wh
unsigned
100
Wh
unsigned
100
Wh
unsigned
100
varh
unsigned
100
varh
unsigned
100
varh
unsigned
varh
unsigned
100
VAh
unsigned
100
VAh
unsigned
100
VAh
unsigned
100
VAh
unsigned
0.01
%
unsigned
0.01
%
unsigned
0.01
%
unsigned
Access
SNMP Variable
Name
R (03)
whL2-100
R (03)
whL3-100
R (03)
wh3-100
R (03)
qhL1-100
R (03)
qhL2-100
R (03)
qhL3-100
R (03)
qh3-100
R (03)
shL1-100
R (03)
shL2-100
R (03)
shL3-100
R (03)
sh3-100
R (03)
thdIL1
R (03)
thdIL2
R (03)
thdIL3
63

Advertisement

Table of Contents
loading

Table of Contents