CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)
—
Product overview
—
Reset button
There is a recessed button to restart the device or for resetting it to a defined as-delivered condition.
• Pressing the button for 3 to less than 6 seconds restarts the device with current settings
• Pressing the button for more than 10 seconds resets the device to the factory settings
Do not switch off the device during the reset process.
—
LEDs
Two LEDs indicate respectively the status of the device and the one of the network.
1. LED Status
Display
Off
Green on
Green flashing slowly
Orange flashing slowly
Orange on
Red on
2. LED Network
Display
Off
Green on
Green flashing
Function
Device is off
Device is ready
Firmware is ready, Web server is loading
Firmware update ongoing
Booting
Booting error
Function
LAN is not connected
LAN is connected
Network traffic