ABB CMS-700 User Manual page 62

Circuit monitoring system
Hide thumbs Also See for CMS-700:
Table of Contents

Advertisement

CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)
Modbus and SNMP Mapping
Addr.
Addr.
Word
Description
(hex)
(dec)
(16-bit)
Branches
3200
12'800
64
Branch name of Sensor 1
3240
12'864
64
Branch name of Sensor 2
...
...
64
...
49C0
18'880
64
Branch name of Sensor 96
5200
20'992
64
Name of Group 1*
5240
21'056
64
Name of Group 2
...
...
64
...
69C0
27'072
64
Name of Group 96
7200
29'184
1
Phase assigned to Sensor 1
7201
29'185
1
Phase assigned to Sensor 2
...
...
1
...
725F
29'279
1
Phase assigned to Sensor 96
7280
29'312
1
Group number of Sensor 1**
7281
29'313
1
Group number of Sensor 2
...
...
1
...
72DF
29'407
1
Group number of Sensor 96
7300
29'440
1
Power Factor of Sensor 1
7301
29'441
1
Power Factor of Sensor 2
...
...
1
...
735F
29'553
1
Power Factor of Sensor 96
Alarm/Event Status – only Status
8000
32'768
1
Number of current alarms
8001
32'769
1
Alarm Status Branch 1
8002
32'770
1
Alarm Status Branch 2
...
...
1
8060
32'864
1
Alarm Status Branch 96
8061
32'865
1
Alarm Status Line L1
8062
32'866
1
Alarm Status Line L2
8063
32'867
1
Alarm Status Line L3
8064
32'868
1
Alarm Status Line L4/N
Alarm/Event Status – Status and Threshold
8100
33'024
1
Number of current alarms
8101
33'025
1
Alarm Status Branch 1
8102
33'026
2
Alarm Threshold Branch 1
8104
33'028
1
Alarm Status Branch 2
8105
33'029
2
Alarm Threshold Branch 2
...
...
821E
33'310
1
AlarmStatusBranch96
821F
33'311
2
AlarmThresholdBranch96
...
...
8221
33'313
1
AlarmStatusLine L1
8222
33'314
2
AlarmThresholdLine L1
8224
33'316
1
AlarmStatusLine L2
8225
33'317
2
AlarmThresholdLine L2
8227
33'319
1
AlarmStatusLine L3
8228
33'320
2
AlarmThresholdLine L3
822A
33'322
1
AlarmStatusLine L4/N
822B
33'323
2
AlarmThresholdLine L4/N
Resolution
Unit
Format
(1-bit value)
64
letter
string
64
letter
string
64
letter
string
64
letter
string
64
letter
string
64
letter
string
64
letter
string
64
letter
string
1
short
1
short
1
short
1
short
1
short
1
short
1
short
1
short
0.01
unsigned
0.01
unsigned
0.01
unsigned
0.01
unsigned
unsigned
unsigned
unsigned
unsigned
unsigned
unsigned
unsigned
unsigned
unsigned
unsigned
unsigned
signed
unsigned
signed
unsigned
signed
unsigned
signed
unsigned
signed
unsigned
signed
unsigned
signed
Access
SNMP
Variable Name
RW (03,10) BranchNameSens1
RW (03,10) BranchNameSens2
RW (03,10) ...
RW (03,10) BranchNameSens96
RW (03,10) GroupName1
RW (03,10) GroupName2
RW (03,10) ...
RW (03,10) GroupName96
RW (03,06) PhaseSens1
RW (03,06) PhaseSens2
RW (03,06) ...
RW (03,06) PhaseSens96
RW (03,06) GroupSens1**
RW (03,06) GroupSens2
RW (03,06) ...
RW (03,06) GroupSensor96
RW (03,06) PowerFactorSens1
RW (03,06) PowerFactorSens2
RW (03,06) ...
RW (03,06) PowerFactorSens96
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
R (03)
61