60
CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)
Modbus and SNMP Mapping
Addr.
Addr.
Word
Description
(hex)
(dec)
(16-bit)
Measured hold values:
These registers contain the hold values captured at a given time during the execution of a "trigger hold measurement" request.
0C00
3'072
1
TRMS hold value of Sensor 1
0C01
3'073
1
TRMS hold value of Sensor 2
...
...
1
...
0C5F
3'167
1
TRMS hold value of Sensor 96
0D00
3'328
1
AC hold value of Sensor 1
0D01
3'329
1
AC hold value of Sensor 2
...
...
1
...
0D5F
3'423
1
AC hold value of Sensor 96
0E00
3'584
1
DC hold value of Sensor 1
0E01
3'585
1
DC hold value of Sensor 2
...
1
...
0E5F
3'679
1
DC hold value of Sensor 96
Serial number (SID), version and bus line
1000
4'096
16
SID, version, bus line of sensor 1
1010
4'112
16
SID, version, bus line of sensor 2
...
...
16
...
15F0
5'616
16
SID, version, bus line of sensor 96
Polarity of sensors (for DC currents)
2000
8'192
1
Polarity of sensor 1
2001
8'193
1
Polarity of sensor 2
...
...
1
...
205F
8'3287
1
Polarity of sensor 96
Calculated values of sensors
2200
8'704
2
P value of Sensor 1
2202
8'706
2
P value of Sensor 2
...
...
2
...
22BE
8'864
2
P value of Sensor 96
2300
8'960
2
Active Energy value of Sensor 1
2302
8'962
2
Active Energy value of Sensor 2
...
...
2
...
23BE
9'150
2
Active Energy value of Sensor 96
Calculated values of sensors
2500
9'472
2
Active Energy value of Group 1
2502
9'472
2
Active Energy value of Group 2
...
...
2
...
25BE
9'662
2
Active Energy value of Group 96
Control registers
3001
12'289
1
Physical assignment of sensor time-out,
UI mode
3002
12'290
1
Physical assignment of sensor time-out,
UI mode
Resolution
Unit
Format
(1-bit value)
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
signed
0.01
A
signed
0.01
A
signed
0.01
A
signed
special
special
special
special
special
special
special
special
1
W
unsigned
1
W
unsigned
1
W
unsigned
1
W
unsigned
0.1
Wh
unsigned
0.1
Wh
unsigned
0.1
Wh
unsigned
0.1
Wh
unsigned
100
Wh
unsigned
100
Wh
unsigned
100
Wh
unsigned
100
Wh
unsigned
0.1
s
unsigned
0.1
s
unsigned
Access
SNMP
Variable Name
R (03)
HOLDTRMSsens1
R (03)
HOLDTRMSsens2
R (03)
...
R (03)
HOLDTRMSsens96
R (03)
HOLDACsens1
R (03)
HOLDACsens2
R (03)
...
R (03)
HOLDACsens96
R (03)
HOLDDCsens1
R (03)
HOLDDCsens2
R (03)
...
R (03)
HOLDDCsens96
R (03)
SIDsens1
R (03)
SIDsens2
R (03)
...
R (03)
SIDsens96
RW
(03,06,10)
POLsens1
RW
(03,06,10)
POLsens2
RW
(03,06,10)
...
RW
(03,06,10)
POLsens96
R (03)
Psens1
R (03)
Psens2
R (03)
...
R (03)
Psens96
R (03)
Whsens1
R (03)
Whsens2
R (03)
...
R (03)
Whsens96
R (03)
WhGroup1
R (03)
WhGroup2
R (03)
...
R (03)
WhGroup96
RW (03,06) uiTIMEOUTsens
RW (03,06) busTIMEOUTsens

Advertisement

Table of Contents
loading