Keypad And Fire Circuit Wiring Information - DSC PC2585 Installation Manual

Software version 1.1r dls-1 v6.2kr and up
Table of Contents

Advertisement

KEYPAD AND FIRE CIRCUIT WIRING INFORMATION

Keypad Hook-up Diagram and Wiring Chart
1 Each keypad has four coloured leads: red (RED), black (BLK), yellow (YEL) and green (GRN). Connect the leads
to the corresponding terminals on the control panel.
2 Up to 5 keypads may be connected in parallel. Do not connect multiple keypads on the same loop.
3 The wiring chart provides the maximum wire run for various wire gauges. Wire run lengths are calculated for the
keypad's maximum current draw (when all keypad lights are ON).
4 For stand-by loading purposes, it is recommended that a current draw of 20mA per keypad be used. 20mA
represents the control panel in the disarmed state with two zones in alarm. NOTE: If more that three keypads are
connected, subtract 60mA from the maximum AUX supply for each keypad in excess of three.
NOTE: If two wires of the same gauge are paralleled, the run length may be doubled. For example, if eight 22AWG
wires (2 RED, 2 BLK, 2 YEL and 2 GRN) are run to the keypad, the run length may be doubled from 540 feet
(164.5 m) to 1080 feet (329 m).
Fire and Bell Circuit Wiring Charts
BELL LOOP WIRING CHART
AWG
Loop
14
Current
mA
Maximum Run to EOL Resistor (ft/m)
50
2750/838
1740/530
100
1375/419
200
690/210
300
460/140
400
345/105
500
275/83
600
230/70
700
195/59
RED BLK YEL GRN
AWG
AWG
AWG
16
18
19
1090/332
869/264
870/265
545/166
435/132
435/132
270/82
217/66
290/88
180/55
144/44
215/65
135/41
108/33
170/52
105/32
86/26
140/43
90/27
72/22
125/38
80/24
62/19
SMOKE DETECTOR POWER LOOP WIRING CHART
AWG
14
Loop
Current
Maximum Run to End of Line Relay
mA
50
4750/1448
100
2375/724
200
1190/363
300
790/241
400
595/181
KEYPAD WIRING CHART
Wire
Gauge
5
1
6
2
7
3
8
AWG24
4
AWG22
AWG20
5
1
6
2
7
3
8
AWG19
4
AWG18
AWG
22
433/131
217/66
144/44
108/33
54/16
43/13
36/11
30/9
AWG
AWG
AWG
16
18
19
(feet/metres)
3000/914
1880/573
1500/457
1500/457
940/287
750/229
750/229
470/143
370/113
500/152
310/94
250/76
375/114
235/72
185/56
Maximum Run Length
Keypad to Panel
(feet/metres)
330 / 100
540 / 164
850 / 259
1000 / 305
1360 / 414
ALARM INITIATING LOOP
WIRING CHART
Maximum Run to
Wire
End of Line Resistor
Gauge
(feet/metres)
AWG14
15500 / 4724
AWG16
9740 / 2968
AWG18
6120 / 1865
AWG19
4860 / 1481
AWG20
3840 / 1170
AWG21
3060 / 932
AWG22
2420 / 737
AWG
22
750/229
370/113
185/56
120/37
90/27
49