Seventh System Option Code; Maximum Dialing Attempts Per Buffer - DSC PC2585 Installation Manual

Software version 1.1r dls-1 v6.2kr and up
Table of Contents

Advertisement

[26]

Seventh System Option Code

Refer to Programming Section [20] for programming instructions.
Zone Light 1
• OFF = Zone 7 is a normal zone
ON = Zone 7 is a Fire Zone. When ON, the Zone Defintion programmed in Section [18] for
• OFF = Not Used
Zone Light 2
Zone Light 3
• OFF = Keypad Lights always ON
ON = Keypad Lights turn OFF after 2 minutes of last key entry. Any alarm, entry delay, or
Zone Light 4
• OFF = Keypad Tamper Disabled. Keypad tamper conditions will not be reported or indicated.
ON = Keypad Tamper Enabled. The Keypad Trouble function, described in "Display Trouble
Zone Light 5
• OFF = Battery Test Every 4 Minutes. The system will perform a battery test every 4 minutes.
ON = Battery Test Every 10 Seconds and Battery Test on Arming. The system will perform battery
Zone Light 6
• OFF = AC Trouble Reported. When OFF, AC troubles will be reported.
ON = AC Trouble Not Reported. When ON, AC troubles will not be reported. Do not use this
Zone Light 7
• OFF = AC supply: 50Hz
ON = AC supply: 60Hz
Zone Light 8
• OFF = Not Used
• = Default setting
Battery Test Function
Battery Test Every 10 Seconds (Zone Light 5 ON). When an Access Code is entered to arm the system, there will be
a 5 second delay before the arming sequence begins. During the delay, a battery test is performed.
• If Power Loss Inhibits Arming is enabled (Section [25] Zone Light 3 ON) the system will not arm if a low battery
condition is present
• If there is a Low Battery Trouble when an Access Code is entered to arm the system, and Power Loss Inhibits Arming
is disabled (Section [25] Zone Light 3 OFF), the system will arm without the 5 second delay for the Battery Test
• If the system is communicating when an Access Code is entered to arm the system, the Battery Test will not be
performed
• During the 5 second Battery Test delay, all keypresses on the keypad will be ignored. If an alarm is generated during
the delay, the bell or siren will sound after the delay. Transmissions are not delayed during the Battery Test delay
Fire Zone Operation
If Section [26] Zone Light 1 is ON, Zone 7 will be defined as a Fire Zone.
The Fire Zone is a 24-hour (normally-open alarm initiating contact) end-of-line resistor zone designed for latching four-
wire smoke detectors. On alarm, the Bell output will pulse to indicate that the Fire Zone has been activated. Alarm
memory and transmission of the alarm are delayed for 30 seconds. If the alarm is acknowledged by pressing any key
before the 30 second delay expires, the bell will silence and the transmission will be cancelled.
After the alarm has been acknowledged, the bell output will be activated again if the smoke detector is not restored
to normal within 90 seconds. The user then has 30 seconds again to silence the bell and abort the transmission before
the bell latches and the communication is initiated. NOTE: Do not program fire zones as silent and do not use
Double EOL resistors with this zone type.
For an open on the Fire Zone, the "Trouble" light will come ON and the keypad sounder will beep every 10 seconds,
regardless of whether the system is armed or disarmed. The trouble condition will be reported if a reporting code is
programmed in Section [16]. The "Trouble" light will only be shut OFF when all of the Fire Zone troubles are corrected.
[27]

Maximum Dialing Attempts per Buffer

Enter three 2-digit numbers in this section to determine the maximum number of dialing attempts for each
communications buffer and the Downloading Telephone Number. Valid entries are in the range of 01 to 99; the default
setting for all numbers is 03. Communications Buffer 1 affects the First and Second Telephone Numbers, and
Communication Buffer 2 affects the Third Telephone Number.
Zone 7 will be ignored. Refer to Fire Zone Operation on Page 27.
keypresses will reactivate the keypad lights. This feature must be OFF when LCD
keypads are used with the PC2585.
Disable Keypad Tamper if LED625T or LCD600T keypads are not being used.
Conditions [ ]+[2]" in the Keypad Functions section of the manual, will be enabled.
test every 10 seconds and when the system is armed.
feature with the "Power Loss Inhibits Arming" feature (Section [25], Zone Light 3 ON)
27