Mounting The Aspirated Sampling Module Unit; (All Models); Caution - MSA Ultima X Instruction Manual

Sampling module, dc aspirated model
Hide thumbs Also See for Ultima X:
Table of Contents

Advertisement

Mounting the Aspirated Sampling Module Unit

(All Models)

1. Locate the Aspirated Sampling Module and the Ultima X Gas
Monitor(s) in a clean, accessible location.
Since the unit enclosure is non-corrosive, it can be mounted to
the outside of a building or in other wet environments.
Use of Teflon tape or non-hardening thread sealant for
environmental reasons is acceptable.
When installing multiple Ultima X Gas Monitors, locate all
monitors within 18 inches (45 cm) of each other.
Ensure that Aspirated Sampling Module or the Ultima X Gas
Monitor unit front covers are not blocked or obscured. A
blocked front cover will obscure the gas reading indication
and sampling module indications. The unit must be mount-
ed with the electrical input facing down and the label clearly
readable.
2. Mount the Aspirated Sampling Module and Ultima X Gas Monitor
to a wall:
From the electrical condulet or
By using optional mounting strap (P/N 10047561) and the four
holes in the rear of the units.
3. Mount Ultima X Gas Monitor SENSOR INLET facing downward
4. Mount Aspirated Sample Module EXHAUST tubing so that the end
of the tubing is facing downward and is the lowest point of the
tubing (see FIGURE 1-1).
The Ultima X Gas Monitor must be mounted with its sensor
at the bottom of the case and the sensor inlet fitting pointed
downward; otherwise, the unit may become inoperative.
2-2

" CAUTION

" CAUTION