1.15 CONCENTRIC HORIZONTAL KIT
INSTALLATION.
Type C configuration, sealed chamber and
fan assisted.
e position of the terminal (in terms of distanc-
es from openings, overlooking buildings, oor,
etc.) must be in compliance with the regulations
in force.
is terminal is connected directly to the outside
of the building for air intake and ue gas exhaust.
e horizontal kit can be installed with the rear,
right side, le side or front outlet. For installation
with frontal outlet, one must use the xing plate
and a concentric bend coupling in order to ensure
su cient space to carry out the tests required by
law upon commissioning.
• External grid. Both the Ø 60/100 and Ø 80/125
intake/exhaust terminal, if properly installed, is
pleasant to look at on the outside of the build-
ing. Make sure that the external silicone wall
sealing plate is properly inserted in the wall.
N.B.: for proper system operation the terminal
with grid must be installed correctly ensuring
that, the "high" indication on the terminal is
observed during installation.
2
1
3
e kit includes:
N° 1 - Gasket (1)
N° 1 - Concentric bend Ø 60/100 (2)
N° 1 - Int./exhaust concentric terminal Ø 60/100 (3)
N° 1 - Internal wall sealing plate (4)
N° 1 - External wall sealing plate (5)
3
4
2
1
e adaptor kit includes:
N° 1 - Gasket (1)
N° 1 - Adapter Ø 80/125 (2)
19
Horizontal intake-exhaust kit Ø 60/100. Kit
assembly (Fig. 17): install the bend with ange
(2) on the central hole of the boiler, positioning
gasket (1) with the circular projections down-
wards in contact with the boiler flange, and
tighten using the screws present in the kit. Fit
the Ø 60/100 (3) concentric terminal pipe with
the male side (smooth) to the female side of the
bend (2) up to the end stop; making sure that the
internal and external wall sealing plate have been
tted, this will ensure sealing and joining of the
elements making up the kit.
• Extensions for Ø 60/100 horizontal kit (Fig. 18).
e kit with this con guration can be extended
up to a max. 12.9 horizontal m including the
terminal with grid and excluding the concen-
tric bend leaving the boiler.
corresponds to a resistance factor of 100. In this
case the special extensions must be requested.
Immergas also provides a Ø 60/100 simpli ed
terminal, which in combination with its ex-
tension kits allows you to reach a maximum
extension of 11.9 metres.
Horizontal intake-exhaust kit Ø 80/125. Kit
assembly (Fig. 19): to install the kit Ø 80/125
one must use the anged adapter kit in order
to install the ue system Ø 80/125. Install the
anged adaptor (2) on the central hole of the
boiler, positioning gasket (1) with the circular
projections downwards in contact with the boiler
ange, and tighten using the screws contained in
the kit. Engage the bend (3) with the male side
(smooth) to the end stop on the adapter (1). Fit
C
13
4
5
17
C
13
5
6
e Kit Ø 80/125 includes:
N° 1 - Concentric bend Ø 80/125
at 87° (3)
N° 1 - Concentric intake-exhaust
terminal Ø 80/125 (4)
N° 1 - Internal wall sealing plate (5)
N° 1 - External wall sealing plate (6)
e remaining kit components
must not be used
the Ø 80/125 (5) concentric terminal pipe with
the male side (smooth) to the female side of the
bend (4) (with lip seals) up to the end top; making
sure that the internal (6) and external wall sealing
plate (7) have been tted, this will ensure sealing
and joining of the elements making up the kit.
• Extensions for Ø 80/125 horizontal kit (Fig. 20).
up to a max. length of 32 m, including the termi-
nal with grid and excluding the concentric bend
leaving the boiler. If additional components
are assembled, the length equivalent to the
maximum allowed must be subtracted. In this
case the special extensions must be requested.
is con guration
15
e kit with this con guration can be extended
C
13
18
C
13
20