Victrix Zeus 20/27 Instructions
VICTRIX ZEUS 20/27
Instruction Booklet
Eco-friendly wall-hung condensing boilers
with stainless steel storage tank
Read these instructions completely before using or installing the
Victrix Zeus 20/27 gas boilers
LEAVE THESE INSTRUCTIONS WITH THE USER
For Technical assistance, spare parts or service call:
RVR Limited, Kenmare, Co. Kerry Tel: 064 41344, Fax: 064 89520
Doc. Ref.: ALT112/171207
Page

Advertisement

Table of Contents
loading

Summary of Contents for Immergas VICTRIX ZEUS 20

  • Page 1 Eco-friendly wall-hung condensing boilers with stainless steel storage tank Read these instructions completely before using or installing the Victrix Zeus 20/27 gas boilers LEAVE THESE INSTRUCTIONS WITH THE USER For Technical assistance, spare parts or service call: RVR Limited, Kenmare, Co. Kerry Tel: 064 41344, Fax: 064 89520 Doc.
  • Page 2: Using The Boiler

    Victrix Zeus 20/27 Instructions Introduction The Victrix Zeus 20/27 boilers are condensing wall hung, room sealed combination boilers incorporating a 54 litre unvented hot water storage cylinder. This boiler has the highest efficiency possible for a gas boiler, ie 4 stars (****) in conformity with European Directive 92/42 EEC.
  • Page 3 Victrix Zeus 20/27 Instructions PERFORMANCE: Victrix 20 Victrix 27 Nominal Heat Input 24.0 32.6 Min. Heat Input Nominal Heat Output (useful) 23.5 Min. Heat Output GAS: Nozzle diameter Supply Pressure Mbar HEATING SYSTEM: Max Operating Pres. of Heating Unit Max Operating Temp. of Heating Unit ºC...
  • Page 4 Victrix Zeus 20/27 Instructions Main Boiler Components Cold Gas System System Return Flow Outlet Inlet 1.Intake sockets (A= air) 13. System filling cock 25.3-bar safety valve (F=fumes) 2.Combustion chamber cover 14.Expansion vessel 26.8-bar safety valve 3.Ignition electrodes 15.Combustion chamber 27.Gaudium Magnum device 4.Detection electrode...
  • Page 5: General Installation Information

    Victrix Zeus 20/27 Instructions General Installation Information Gas Supply The meter and supply pipes must be sized to deliver the gas rate and pressure given on page 3. boiler requires at least a 22 mm (3/4”) gas supply pipe. The complete installation, including the meter, must be tested for gas soundness and purged as described in IS 813:2002.
  • Page 6: Flue Systems

    This is shown in the diagram. It is often necessary to install a longer flue system to cater for site conditions. There are several different flue system sizes available for the Victrix Zeus 20/27 boiler. Horizontal concentric kit 60 /100...
  • Page 7 Victrix Zeus 20/27 Instructions Separated Flue Systems Separated 80/80 flue kit This kit enables separation of the exhaust and air intake pipes as shown in the figure. Combustion products are expelled from pipe (A) (in plastic material resistant to acidic condensates). Air is taken in through pipe (B) (also in plastic material) for combustion.
  • Page 8 Victrix Zeus 20/27 Instructions Flue calculations for more complex systems Each component of the air inlet/flue system has a resistance factor . These are given in the following tables. The resistance factor varies depending on whether the component in question conveys fresh inlet air or hot combustion gases.
  • Page 9 Victrix Zeus 20/27 Instructions Example: Flue system consists of 9m of 80mm air intake pipe with 3 x 90˚ bends and 6m of exhaust pipe with 2 x 90˚ bends. Component Resistances: Component Resistance Quantity Total In this case the total resistance of the 80mm Intake pipe 0.87...
  • Page 10 Victrix Zeus 20/27 Instructions Terminal Position Min. Distance A Directly below an opening, air brick, windows, etc. 300 mm B Below gutters, soil pipes or drain pipes 75mm C Below eaves 75mm D Below balconies or car port roof 75mm...
  • Page 11: Boiler Location

    Victrix Zeus 20/27 Instructions Boiler Location The boiler is not suitable for external installation. The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler. The boiler can be fitted to or adjacent to a wall comprising of a combustible material without the need for a special thermal insulation barrier.
  • Page 12: Central Heating System

    Victrix Zeus 20/27 Instructions Central Heating System The boiler is designed for use in a sealed central heating system. The system should be designed to oper- ate with flow temperatures of up to 80°C. When designing the system, the pump head, expansion vessel size, mean radiator temperature, etc.
  • Page 13: Filling The Central Heating System

    Victrix Zeus 20/27 Instructions The most important components of the system are shown in the diagram below. The cold water supply for the water heating side of the system may come from a booster pump or the • cold water mains where this is permitted by the local authority.
  • Page 14: Domestic Hot Water System

    The installation is subject to Building Regulations and the Water Bye Laws of the Local Authority. The Victrix Zeus 20/27 boiler is supplied with all the components required for a safe and efficient unvented hot water system. An air cushion which is present at the top of the 54l storage vessel provides some of the expansion for the domestic hot water system.
  • Page 15 Victrix Zeus 20/27 Instructions Tundish installation The discharge pipework from the tundish:- 1. Shall fall continuously through its length. 2. Shall be of a heat resistant material, e.g. metal. 3. Shall not be fitted with any valves or taps. 4. Shall discharge to a safe visible position, e.g. onto the surface of an external wall or into a gulley.
  • Page 16: Electrical Safety

    Victrix Zeus 20/27 Instructions Operation and Maintenance Instructions An annual maintenance of the boiler and heating system is recommended. This ensures that the optimal safety, performance and operation characteristics of the boiler remain unchanged over time. Warnings Never expose the wall-mounted boiler to direct vapours from a cooking surface. Use of the boiler by un- skilled persons or children is strictly prohibited.
  • Page 17: Reset Button

    Victrix Zeus 20/27 Instructions Operation and Maintenance Instructions Boiler display and indicators DL1 - Green LED that comes on when the boiler is operating in heating or antifreeze mode. DL2 - Green LED that comes on when the boiler is working in domestic hot water mode.
  • Page 18: Maintenance Operations

    Victrix Zeus 20/27 Instructions Maintenance Operations: Lack of water in boiler. Not enough water pressure detected in the heating circuit to guarantee correct boiler operation. Make sure that the pressure in the system is between 1and1.2 bar. N.B. Close the valve on completion. If pressure valves reach around 3 bar the safety valve may be activated.
  • Page 19: Annual Maintenance Procedures

    Victrix Zeus 20/27 Instructions Annual maintenance procedures The following checks and maintenance should be performed at least once a year. - Clean the flue side of the heat exchanger. - Clean the main burner. - Make a visual inspection of the flue extraction hood for wear or corrosion.
  • Page 20: Variable Heat Output

    Victrix Zeus 20/27 Instructions Variable Heat Output: Victrix 20: N.B.: Pressure values specified in the table indicate the difference of pressure values between the gas valve outlet and the combustion chamber. Adjustments are carried out using a differential pressure gauge...
  • Page 21 Victrix Zeus 20/27 Instructions Victrix Zeus 20/27 Wiring Diagram: Page 21...