3.7 CHECKS FOLLOWING
CONVERSION TO ANOTHER TYPE
OF GAS.
A er making sure that conversion was carried
out with a nozzle of suitable diameter for the
type of gas used and the settings are made at the
correct pressure, check that the burner ame is
not too high or low and is stable (does not detach
from burner);
N.B.: all boiler adjustment operations must be
carried out by a quali ed technician (e.g. Ah-
thorized A er-Sales Assistance).
Victrix Tera 24 Plus
CO
at maximum
CO
2
2
output
9.70 %
G 20
+ 0.50 / - 0,20
+ 0.20 / - 0.30
G 31
11.40 % ± 0,30
10.60 % ± 0.20
Attention: check the serial number on the boiler.
From number 7211394 use the data in the fol-
lowing table.
Victrix Tera 24 Plus
CO
at maximum
CO
2
2
output
9.70 %
G 20
+ 0.30 / - 0,20
+ 0.20 / - 0.30
G 31
11.40 % ± 0,30
10.60 % ± 0.20
at minimum
output
8.80 %
at minimum
output
8.80 %
32