A test connector with the connections shown below is required for this
test.
Set test connector set up as follows:
1. Connect 4, 16, 17, 18, 19, 27, 29, 32 and 33.
2. Connect 5 and 12.
3. Connect 39, 20 and 55.
4. Connect 42 and 60.
5. Connect 45, 53 and 54
Test the control card in accordance with the following procedure:
1. Select Control Card Test.
2. Remove input power and wait for light in display to go out.
3. Insert test connector described above.
4. Reconnect input power.
5. Press OK key. (Test cannot run without control panel in place.)
6. Drive automatically tests control card.
7. Remove test connector and press OK key when drive displays
“TEST COMPLETED.”
8. Parameter 620, Operating Mode, is automatically set to Normal
Function.
If the control card test fails, the drive will display “TEST FAILED.”
Replace the control card.
Initialization is selected to reset the drive to its factory default settings
without resetting parameters 501 Address, 502 Baud Rate; 600-605,
Operating Data; and 615-617, Fault Log.
Choosing Initialization resets drive to standard
default values. Any special application
programming performed at the factory, during
start-up, or thereafter, will be lost. As a backup,
upload drive settings into the driveís local
control panel (LCP) keypad as described in
parameter 004, LCP Copy.
Initialization the drive to factory default settings in accordance with the
following procedures:
1. Select Initialization.
2. Press OK key.
3. Remove input power and wait for light in display to go out.
4. Connect input power.
5. Initialization of all parameters will be carried out in all Setups with
exception of parameters 501, Address; 502, Baud Rate;
600-605, Operating Data; and 615-617, Fault Log.
NOTE
91