It is very important that values set in parameters
102, Motor Power, through 106, Rated Motor
Speed, correspond accurately to nameplate data
of motor. Failure to enter motor nameplate data
accurately could result in erratic or less than
optimum equipment operation.
102
Motor Power
Value:
0.25 kW
(0.33 HP)
0.37 kW
(0.5 HP)
0.55 kW
(0.75 HP)
0.75 kW
(1 HP)
1.1 kW
(1.5 HP)
1.5 kW
(2 HP)
2.2 kW
(3 HP)
3 kW
--
4 kW
(5 HP)
5.5 kW
(7.5 HP)
7.5 kW
(10 HP)
11 kW
(15 HP)
15 kW
(20 HP)
18.5 kW
(25 HP)
22 kW
(30 HP)
30 kW
(40 HP)
37 kW
(50 HP)
45 kW
(60 HP)
55 kW
(75 HP)
75 kW
(100 HP)
90 kW
(125 HP)
110 kW
(150 HP)
132 kW
(175 HP)
160 kW
(200 HP)
200 kW
(300 HP)
250 kW
--
300 kW
--
315 kW
(350 HP)
355 kW
(450 HP)
400 kW
(500 HP)
450 kW
(600 HP)
★ Depends on the unit
Function:
Set the power value that corresponds to the nameplate power of the
motor. The default setting is the full rating of the drive.
Description of choice:
Select a value that equals the nameplate data on the motor. It is also
possible to set any power within the range of the drive.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
NOTE
(MOTOR POWER)
[25]
[37]
[55]
[75]
[110]
[150]
[220]
[300]
[400]
[550]
[750]
[1100]
[1500]
[1850]
[2200]
[3000]
[3700]
[4500]
[5500]
[7500]
[9000]
[11000]
[13200]
[16000]
[20000]
[25000]
[30000]
[31500]
[35500]
[40000]
[50000]
103
Motor Voltage
Value:
200 V
208 V
220 V
230 V
240 V
380 V
400 V
415 V
440 V
460 V
480 V
500 V
575 V
★ Depends on the unit
Function:
Set the rated motor voltage.
Description of choice:
Select a value that equals the nameplate data on the motor. This may
be less than the input voltage. It is also possible to set any voltage
within the range of the drive.
104
Motor Frequency
Value:
50 Hz (50 Hz)
★ 60 Hz (60 Hz)
Function:
This is where the rated motor frequency is selected. This is usually the
frequency of the power line.
Description of choice:
Select the desired value. It is also possible to set any frequency within
the range of the drive.
Failure to enter motor nameplate data
accurately could result in erratic or less than
optimum equipment operation. Also, changing
values in parameter 102, Motor Power, or
parameter 103, Motor Voltage, after motor
current has been entered in parameter 105, may
automatically change the value in parameter 105.
105
Motor Current
Value:
0.01 to drive rating
Function:
The rated motor current in amps is used for setting output current and
providing motor thermal protection. It is important to set the motor
current to the full load current rating (FLA) of the motor.
Description of choice:
Set a value that equals the nameplate data on the motor.
(MOTOR VOLTAGE)
[200]
[208]
[220]
[230]
[240]
[380]
[400]
[415]
[440]
[460]
[480]
[500]
[575]
(MOTOR FREQUENCY)
[50]
[60]
NOTE
(MOTOR CURRENT)
★ Set based on motor nameplate.