014
Auto Start on LCP
Value
Disable (DISABLE)
★ Enable (ENABLE)
Function:
This parameter allows disabling the Auto/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Auto/Start key will be
disabled.
P
015
Reset on LCP
Value:
Disable (DISABLE)
★ Enable (ENABLE)
Function:
This parameter allows disabling the Reset key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Reset key will be inactive.
Do not disable Reset on LCP in parameter 015
unless a remote reset is available through
digital inputs and parameters 300 through 307.
016
Lock for Data Change (DATA CHANGE LOCK)
Value:
★ Not Locked (NOT LOCKED)
Locked (LOCKED)
Function:
This parameter allows locking out parameter changes at the local
control panel.
Description of choice:
If Locked is selected, data modifications in the parameters cannot be
made. Parameter changes will be possible through serial communica-
tion.
Parameters 007 through 010, Display Readout can be changed at the
local control panel.
The local control panel can also be locked or unlocked by a digital
input controlled by parameters 300 through 307.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
(AUTO START BTTN)
[0]
[1]
(RESET BUTTON)
[0]
[1]
NOTE
[0]
[1]
017
Operating State at Power Up
(POWER UP ACTION)
Value:
★ Auto restart (AUTO RESTART)
OFF/STOP (OFF/STOP)
Function:
Selects auto or manual restart when power is reapplied after an outage
occurs to a running drive.
Description of choice:
Auto restart is selected if the drive is to resume operation after a power
015
outage.
OFF/STOP is selected if the drive is to remain stopped after a power
outage. To restart, press the Hand/Start or Auto/Start key at the
keypad. If HAND START or AUTO START are disabled by
parameters 012 and 014, the motor will not be able to restart if OFF
STOP is selected in parameter 017.
[0]
[1]
37