Trane TR1 6002 Installation And Operation Manual page 34

Tr1 series. variable frequency drive
Table of Contents

Advertisement

005
Maximum Value of Custom Readout
(CUSTOM READOUT )
Value:
0.01 to 999,999.99
Function:
This parameter determines the value that the user defined meter will
display when the drive’s output frequency is the value set in parameter
202, Output Frequency High.
Description of choice:
Set the required value for maximum output frequency.
006
Custom Readout
(CUST. READ. UNIT)
Value:
No unit
[0]
%
[1]
rpm
[2]
ppm
[3]
pulse/s
[4]
l/s
[5]
l/min
[6]
l/h
[7]
kg/s
[8]
kg/min
[9]
kg/h
m3/s
[11]
m3/min
[12]
m3/h
[13]
m/s
[14]
mbar
[15]
1
bar
[16]
1
Pa
[17]
1
MPa
[18]
1
MWG
[19]
1
kW
[20]
2
Squared units (pressure)
1
Cubed units (power)
2
Function:
The value and the unit are shown in display mode whenever Custom
Readout has been selected in one of parameters 007 through 010,
Display Readout. If flow or speed units are selected, the relationship
between readout and output frequency will be a linear one. If pressure
units are selected, the ratio will be square. If power units are selected,
the ratio will be cubed.
Description of choice:
Select the required unit for Custom Readout.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
34
✭100.000
GPM
[21]
gal/s
[22]
gal/min
[23]
gal/h
[24]
lb/s
[25]
lb/min
[26]
lb/h
[27]
CFM
[28]
ft3/s
[29]
ft3/min
[30]
[10]
ft3/h
[31]
ft3/min
[32]
ft/s
[33]
in wg
[34]
1
ft wg
[35]
1
PSI
[36]
1
lb/in
[37]
1
HP
[38]
2
007
Large Readout
Value:
None
Reference [%] (REFERENCE [%])
Reference [unit] (REFERENCE [UNIT])
Frequency [Hz] (FREQUENCY [HZ])
✭ Frequency [%] (FREQUENCY [%])
Motor current [A] (MOTOR CURRENT [A])
Power [kW] (POWER [KW])
Power [HP] (POWER [HP])
Output energy [kWh] (ENERGY [KWH])
Hours run [Hours] (HOURS RUN [h])
Custom readout [unit] (CUSTOM READ [UNITS])
Setpoint 1 [unit] (SETPOINT 1 [UNITS])
Setpoint 2 [unit] (SETPOINT 2 [UNITS])
Feedback 1 (FEEDBACK 1 [UNITS])
Feedback 2 (FEEDBACK 2 [UNITS])
Feedback [unit] (FEEDBACK [UNITS])
Motor voltage [V] (MOTOR VOLTAGE [V])
DC link voltage [V] (DC VOLTAGE [V])
Thermal motor load [%]
(THERM.MOTOR LOAD [%])
Thermal drive load [%] (THERM.DRIVE LOAD [%]) [19]
Digital input [Binary code] (DIGITAL INPUT [BIN])
Analog input 53 [V] (ANALOG INPUT 53 [V])
Analog input 54 [V] (ANALOG INPUT 54 [V])
Analog input 60 [mA] (ANALOG 60 [mA])
Relay status [Binary code] (RELAY STATUS [BIN])
Pulse reference [Hz] (PULSE REFERENCE [Hz])
External reference [%] (EXT. REFERENCE [%])
Heat sink temp. [
C] (HEATSINK TEMP [
o
Profibus fault [HEX] (COMM.OPTION WARN [HEX]) [28]
Free program array [text] (FREE PROG. ARRAY)
Status word (STATUS WORD [HEX])
Control word (CONTROL WORD [HEX])
Alarm word (ALARM WORD [HEX])
(LARGE READOUT)
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
C])
[27]
o
[29]
[30]
[31]
[32]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents