After the L
W
communication module has been installed,
on
orks
the MicroTech III chiller unit controller is ready for integration
into a building automation system (BAS). The following
section explains how the communication module, together
with the unit controller, support L
requirements. It then provides instructions for commissioning
and configuring the communication module.
L
W
Network Addressing
on
orks
The L
W
communication module conforms to the network
on
orks
addressing rules as described in the L
Free Topology Transceiver Users Guide (www.echelon.com).
According to the standard, all device addresses are defined at
the time of network configuration. Device addresses have three
parts:
1. The Domain ID - designates the domain. Devices must
be in the same domain in order to communicate with
each other.
2. The Subnet ID - specifies a collection of up to 127
devices that are on a single channel or a set of channels
connected by repeaters. There may be up to 255
subnets in a domain.
3. The Node ID - identifies an individual device within the
subnet.
A group is a logical collection of devices within a domain.
Groups are assembled with regard for their physical location
in the domain. There may be up to 256 groups in a domain. A
group address is the address that identifies all devices of the
group. There may be any number of devices in a group when
unacknowledged messaging is used. Groups are limited to 64
devices if acknowledged messaging is used.
A broadcast address identifies all devices within a subnet or
domain.
External Interface File (XIF) and NXE
Files
The L
W
communication module conforms to LonMark
on
orks
guidelines. It is self-documenting so that any L
network management tool can be used for integration and

configuration.

An external interface file (a specially formatted PC text file
with the extension .XIF) is required, along with a L
network management tool, so the device can be designed and
configured prior to installation.
The NXE file contains the application image that is downloaded
into the L
W
communication module.
on
orks

Resource Files

Resource files contain definitions of functional profiles,
network variables types, configuration property types, and
enumerations. Resource files are required for displaying Daikin
Applied-specific variables that are not included in the standard
device profile. The L
W
on
orks
McQuayChiller (Scope 5) resource files.
IM 968-4 • MICROTECH III CHILLER UNIT CONTROLLER
W
network addressing
on
orks
W
FTT-10A
on
orks
W
on
orks
W
on
orks
communication module uses the
C
The XIF, NXE, and Resource files are available
at
www.DaikinApplied.com

Commissioning

Follow these steps to commission the L
communication module:
1. Verify the communication module is attached properly to
the unit controller.
2. Connect the twisted pair cable to the communication
module's network connector pins CLA and CLB
(Figure
4).
3. Download XIF, NXE, and Resource Files from either
www.DaikinApplied.com
4. Use a L
W
network configuration tool, such as
on
orks
LonMaker
, to map the device Neuron ID to the domain/
®
subnet/node logical addressing scheme when it creates
the network image, the network address, and connection
information.
5. Confirm that the BAS is ready to receive a network
device broadcast message.
6. Press the service pin button. Do this by inserting the end
of a 5/64" (2.0 mm) flathead screwdriver, Allen wrench,
or similar tool with a narrow end, approximately 1.5
inches (3.8 cm) into the small hole to the left of the LEDs
(Figure
5).
At this point, the initialization process begins. See
Table 1
and
Table 2
LED activity. Once both LEDs turn a steady green,
the module is capable of communicating between
both the unit controller and the L
NOTE: Always cycle power to the unit controller after 1)
commissioning a device, 2) de-commissioning an
existing device, and 3) subsequent re-commissioning
of an existing device.
Configuration
There are certain parameters that can be configured using the
unit controller keypad/display. These variables are described
in
Table
3. As a general rule, the L
module does not require configuration unless advised by the
network administrator.
NOTE: Receive Heartbeat, Max Send Time, and Min Send
Time are typical parameters that may need to be
changed for your network. They should be modified
on an as-needed basis. Maintain default values if
possible.
The following steps describe how to set Receive Heartbeat for
your network. The same procedure can also be applied to Max
Send Time and Min Send Time.
10
C
ommIssIonIng and
onfIguraTIon
C
ommIssIonIng and
or www.lonmark.org.
W
on
orks
or www.lonmark.org.
for descriptions of BSP and BUS
W
network.
on
orks
W
communication
on
orks
www.DaikinApplied.com
C
onfIguraTIon