Fault Code Table:
Fault Condition
LCD Touch Panel
Disconnect short-circuited
Output Short
loads and restart the UPS
Circuited
again.
Disconnect all output loads
Overload Fault
and restart the UPS again.
Over Charge Fault
Call for service immediately.
Battery Too Low
Please replace the battery
Fault
(batteries).
Battery Mode Output
Call for service immediately.
High Fault
1. Turn off the UPS and wait
for cooling.
Over Temperature
2. Or remove excessive
loads and wait for cooling.
If any fault alarm occurs, please call for service immediately.
6
Safety Caution
SAVE THESE INSTRUCTIONS-This quick guide contains important
instructions that should be followed during installation and
maintenance of the UPS and battery (batteries).
y y
The UPS utilizes voltage that may be hazardous. Do not attempt to dis-
assemble the unit. The unit contains no user replaceable parts. Only fac-
tory service personnel may perform repairs.
y y
This pluggable type A equipment with battery (batteries) already installed
by the supplier is operator installable and may be operated by laymen.
y y
The mains socket outlet that supplies the UPS shall be installed near the
UPS and shall be easily accessible.
y y
During the installation of this equipment it should be assured that the
sum of the leakage current of the UPS and the connected loads does
not exceed 3.5mA.
y y
Connection to any other type of receptacle other than a two-pole, three-
wire grounded receptacle may result in shock hazard as well as violate
local electrical codes.
y y
In the event of an emergency, press the ON/ OFF Button and disconnect
the power cord from the AC power supply to properly disable the UPS.
y y
Do not allow any liquid or any foreign object to enter the UPS. Do not
place beverages or any other liquid-containing vessels on or near the
unit.
y y
The unit is intended for installation in a controlled environment (tempera-
ture controlled, indoor area free of conductive contaminants). Avoid in-
stalling the UPS in any location where there is standing or running water,
or excessive humidity.
y y
Do not plug the UPS input into its own output.
y y
Do not attach a power strip or surge suppressor to the UPS.
y y
Do not attach non-computer-related items, such as medical equipment,
life-support equipment, microwave ovens, or vacuum cleaners to the
UPS.
y y
Do not dispose of battery (batteries) in a fire as they may explode.
www.deltapowersolutions.com
y y
A battery can present a risk of electrical shock and high short circuit cur-
rent. The following precautions should be observed when working on bat-
Solutions
teries:
1. Remove watches, rings, or other metal objects from the hands.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of battery (batteries).
5. Disconnect charging source prior to connecting or disconnecting
the terminals of battery (batteries).
y y
Internal battery voltage is 12Vdc. Battery type is sealed, lead-acid, 6-cell
battery.
y y
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthor-
ized personnel away from batteries.
y y
When replacing battery (batteries), replace with the same number and
type of sealed lead-acid battery (batteries).
y y
Do not open or mutilate the battery or batteries. Release electrolyte is
harmful to the skin and eyes. It may be toxic.
y y
Attention! Hazardous through electric shock. Even disconnection of this
unit from the mains, hazardous voltage still may be accessible through
supply from the battery (batteries). The battery supply should be therefore
disconnected in the plus and minus pole at the connectors of the battery
(batteries) when maintenance or service work inside the UPS is neces-
sary.
y y
To reduce the risk of overheating the UPS, do not cover the UPS's cooling
vents and avoid exposing the unit to direct sunlight or installing the unit
near heat emitting appliances such as heaters or furnaces.
y y
Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
7

Troubleshooting

Problem
LED doesn't
illuminate
or nothing
is displayed
on the LCD
panel.
The UPS
always runs
in battery
mode.
The UPS
continuously
beeps.
Backup time
is too short.
If any abnormal situations occur that are not listed above, please call for
service immediately.
Possible Cause
Solutions
Press the ON/ OFF Button again to
The UPS is not on.
turn on the UPS.
Battery voltage is too
Charge the battery (batteries) at
low.
least 6 hours.
Battery fault.
Replace the battery (batteries).
The power cord
Re-plug the power cord.
becomes loose.
Replace the fuse. For how to
The fuse is damaged.
replace the fuse, please refer to
.
3
Operation
Please check the
Please check the Fault Code Table
Fault Code Table for
for the details.
the details.
Battery voltage
Charge the battery (batteries) at
is too low.
least 6 hours.
Remove some unnecessary loads.
Before reconnecting equipment,
Overload.
please verify that the load matches
the UPS capability specified in the
specs.
Battery defect.
Replace the battery (batteries).
8

Technical Specifications

Model
600VA
1000VA
Capacity
600VA/360W
1kVA/600W
Nominal
230 Vac
Input Voltage
Input Voltage Range
170 ~ 280 Vac
Output Voltage
230 Vac ± 10% (Bat. mode)
Transfer Time
Typical 2 ~ 6 ms
Waveform
Simulated Sine Wave
Battery Type & No.
12V/7Ah x 1
12V/7Ah x 2
Charging Time
Typical 6 ~ 8 hours
Dimensions
279 x 101 x
320 x 130 x 182 mm
(D x W x H)
142 mm
Net Weight (kgs)
4.2
8.2
Humidity
0 - 90% RH @ 0 - 40°C (non-condensing)
Noise Level
Less than 40dB
* Specifications are subject to change without notice.
9
Warranty
Seller warrants this product, if used in accordance with all applicable
instructions, to be free from original defects in material and workmanship
within the warranty period. If the product has any failure problem within the
warranty period, Seller will repair or replace the product at its sole discretion
according to the failure situation.
This warranty does not apply to normal wear or to damage resulting from
improper installation, operation, usage, maintenance or irresistible force (i.e.
war, fire, natural disaster, etc.), and this warranty also expressly excludes
all incidental and consequential damages. Maintenance service for a fee is
provided for any damage out of the warranty period. If any maintenance is
required, please directly contact the supplier or Seller.
WARNING:
The individual user should take care to determine prior to use
whether the environment and the load characteristic are suitable,
adequate or safe for the installation and the usage of this product.
The Quick Guide must be carefully followed. Seller makes no
representation or warranty as to the suitability or fitness of this
product for any specific application.
Copyright © 2017 by Delta Electronics Inc. All Rights Reserved.
This Quick Guide is subject to change without prior notice.
Version Date : 2017_08_16
1500VA
1.5kVA/900W
12V/7Ah x 2
9.7