Selecting "Save" saves all profiles to the control.
4.
Select Save. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 418:
Save to Device Confirmation Screen
5.
Select OK. TCC600 will display a "Setpoints Successfully Written to Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 419:
Setpoints Successfully Written To The Control Confirmation
Screen

Reverse power operation

The importance of the correct operation of the counter extends beyond mere counting
operations. One additional feature of the control is distinct "reverse power" operations
depending on power flow direction. In addition to normal configurations of "block" or
"ignore" during automatic reverse power detection, the control may be configured to
"regulate in reverse direction" or "return to the neutral position." The control includes a
power direction function for detecting the reversal of power flow in the regulator or
transformer. The active power direction is based on the flow of real power and is not
confused by reactive power flow in either direction.
Section 7
Setpoints
525