1VAC388793-MB A
Appendix B Setpoint, Configuration and Communication Record Forms
Inputs and Switch
Input Selection 1
Input Selection 2
Input Selection 3
Auto/Man Switch Type
Regulator
Remote Voltage Bias (RVB)
RVB Scale Factor
RVB Heartbeat Timer
Reverse RVB Scale Factor
Run Through Neutral (RTN)
Maximum Allowed Taps
Tap Operations Between Runs
Maximum Load Current
Max RTN Standby Operations
Fast Voltage Recovery
Fast Voltage Recovery
TCC300
User Manual
Input Selection 1 must be set to "Switch Status" if Tap Position
Knowledge is to be selected to either "Contact KeepTrack
"Contact KeepTrack 1N".
Switch Status
[Switch Status]
Non-sequential
[Non-sequential]
VR2 [VR2]
None [None]
Type A [Type A]
Disable [Disable]
0.1 to 100.0 [1.0]
2 to 120 (sec) [5]
0.1 to 100.0 [1.0]
Disable [Disable]
3 to 7 [4]
10 to 10000 [1000]
1 to 200 (mA) [50]
1 to 10000 [20]
Disable [Disable]
1.0 to 15.0 (V) [5.0]
Seal-In Input
SCADA Cutout
Aux
Toggle
SCAMP
Type B
Enable
(_______________)
(_______________)
(_______________)
Enable
(_______________)
(_______________)
(_______________)
(_______________)
Enable
(_______________)
Section 11
TM
1R1L" or
659