Section 3
Operation
36
Oscillograph Record Triggered Screen
If the "ENABLE OSC Message" feature is enabled (default setting is Enabled) and the
Oscillograph has been triggered, a cycling display indicating that there is an oscillograph
record available for download will be displayed. The screen will be displayed until the
oscillograph record is cleared or the "ENABLE OSC Message" is disabled. However, if
the Oscillograph file is not cleared, re-enabling this feature will restart the cycling.
The "Oscillograph Record Triggered" cycling display can be enabled from the TCC600
Communications Software by navigating to the "Front Panel Message" (Setup/
Oscillograph/Front Panel Message) dialog screen and selecting "Enable". It can also be
enabled from the HMI by navigating to the "Communication HMI" menu.
GUID-AD7616A3-48B4-470D-B84F-0A0543ADD728 V1 EN
Figure 5:
Oscillograph Message Dialog Screen
Wakeup Message Screens
If the "Wake/EXIT" pushbutton is selected, then control will respond as follows:
When the User Lines are being displayed press "WAKE/EXIT" to initiate a stepped
display of the selected Wakeup parameters for a period of 15 minutes.
If no Wakeup screens are selected, then no parameters will be displayed and the User
Lines will blink for a moment.
The Adapter Panel Drag Hand Reset only resets the Tap Position Drag
Hands.
During the stepped parameter display, pressing ENT on any Demand Metering value
will reset ALL Demand Metering Drag Hand values. This is also true for ALL Energy
Metering Drag Hand values.
The Wakeup stepped display can be stopped on the displayed parameter by selecting
EXIT. Select EXIT again to terminate the stepped parameter display and return to the
User Lines. The Wakeup screen values can be browsed by utilizing the Up and Down
1VAC388793-MB A
TCC300
User Manual