Advertisement

Section 6
Configuration
6.5.1.2
478
The cursor will be positioned under the far right hand zero which
corresponds to LOCAL VOLTAGE. The remaining Data Log
parameter selections are displayed by moving the cursor to the left.
6.
Utilizing the arrow pushbuttons enter a "1" for those Data Log parameters to be
activated and a "0" for those that are to be disabled, then press the ENT pushbutton.
7.
Press the Down arrow pushbutton, as necessary, until the "Data Log Interval" screen
is displayed.
8.
Utilizing the arrow pushbuttons, enter the desired "Data Log Interval" (0 to 120
minutes in 1 minute increments), then press the ENT pushbutton.

Setting up Data Logging from TCC600

1.
Select Setup/Data Logging/Setup from the TCC600 toolbar. TCC600 will display
the Data Logging screen.
GUID-CF69965E-8DF7-4CE6-B1F3-146B6168A4D5 V1 EN
Figure 380:
Data Logging Setup Dialog Screen
The Data Logging Setup dialog screen contains a self calculating
Duration parameter that represents the number of Days and the
specific time when the data logging buffer will be full. The number
of parameters selected to log and the Data Log Interval are
considered in this calculation.
2.
Enter a Data Log Interval (0 to 120 minutes).
3.
Select Save. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
1VAC388793-MB A
TCC300
User Manual