Ratios Display

From the Ratios display we can see the crest factor for each phase, the current % of full load for both each phase
and for the total unit. Additionally, the load in kVA/kW is provided. See Figure 3-11.
Continuing to press the soft key #1 (Multiple Documents icon) will restart the display sequence of all of the measure-
ment displays, i.e., battery, power, current, voltage, frequency and finally ratios.
At this point, it would be appropriate to press the Main Menu key and select the Mimic Diagrams item. This is done
by pressing either soft key #1 or soft key #2 until the item is backlit, and then pressing soft key #4 to select the item
for display. See Figure 3-11.
Figure 3-11: Ratios.
Ratios
Crest Factor
Ph1
1.5
Ph1
1.5
Ph1
1.5
Load
kW/kVA
kW percent load

3.2.10 Mimic Diagrams

The Mimic Diagrams display is unlike any of the other display we have examined. This display is actually two displays
in one. The top half of the display contains a single line representation of the current operating condition of the
Galaxy 3000 unit. Through the use of color changes in the display, it will indicate whether the unit is operating
normally, is on bypass, or is currently running on batteries. The lower half of the display will show any existing alarm
conditions that are present.
To exit this display, it is necessary to press the Main Menu key.
From the Main Menu we can select the Status option. See Figure 3-12.
Figure 3-12:
Mimic Diagram.
NORM Load Protected
D E
L
86-172010-00 C05
%Load
13 %
13 %
13 %
0.8
12 %
Operation
Installation and User Manual
3 —9

Hide quick links: