STEP 2 Connect the Main Utility Power

All Galaxy 3000 UPS systems provide the option for dual (redundant) utility power inputs. Whether the single or
dual inputs are selected, the connection of the utility feed is made to the same terminal block strip in the Galaxy
3000 UPS system.
From the diagram Figure QS-2 below, it can be seen that the main power feed to the Galaxy 3000 system should
be connected to the terminal blocks TB1 on the right hand side of the strip. If a bypass AC source is available (and
the unit was specified to include a second AC source), this power should be connected to the middle set of terminal
blocks TB3.
If the Galaxy 3000 system was specified for a second (bypass) AC source, but a separate power source is not
available, then jumpers should be installed from the primary AC source to the terminal blocks for the bypass AC
source.
NOTE
Figure QS-2: Utility Power Connection.
BOTTOM ENTRY
CONDUIT PLATE
86-172010-00 C05
The three phase power should be supplied as a Wye with a separate
neutral that will be connected to the input neutral busbar.
If the second (bypass) AC source if provided from a source other than
that of the main input, it is recommended to use isolation transformers
so that the neutral of both AC sources can be grounded to the same
potential.
UPS OUTPUT
(TB2)
GROUND TERMINAL POSTS
(INPUT & OUTPUT)
FRONT VIEW
1/4-20 X 3/4" DIA.
(UTILITY2)
BYPASS INPUT
(TB3)
(OPTIONAL)
MAIN INPUT
CONNECTIONS
(TB1)
TERMINAL BLOCK
INPUT NEUTRAL
TERMINAL POST
1/4-20 X 3/4" DIA.
OUTPUT NEUTRAL
TERMINAL POST
1/4-20 X 3/4" DIA.
Quick Start
Installation and User Manual
QS—3