3. Operation
3.1 Turning on the PMM module
1. Close the upstream switching device (external and not supplied) on the circuit supplying the PMM module.
2. In a module with an isolation transformer, close ("I" or ON position) circuit breaker Q1 5 (see page 7) .
3. Make sure disconnector-fuses F1 and F2 are closed and close ("I" or ON position) circuit breaker Q2 5 (see page 7) .
The system status LED 17 (see page 8) flashes yellow a few seconds, then green and should subsequently remain
green.
After a few seconds, the first page of measurements is displayed:
Ph-A
BCM
4. Close the circuit breakers on the output circuits to be powered.
3.2 Display
The display unit for the PMM module offers three operating modes: metering, alarm and setup.
Metering mode
This is the default mode.
Ph-A
CH01
0.000
BCM
CH02
0.000
UP
BCM
CH42
DOWN
METER
Ph-B
CH01
0.000
BCM
CH02
0.000
UP
BCM
CH42
DOWN
METER
Ph-C
CH01
0.000
BCM
CH02
0.000
UP
BCM
CH42
DOWN
METER
GENE
KWH
0000.0
MCM
KW
0000.0
UP
MCM
MAX
DOWN
METER
Page 16 -
34020201EN/AB
All manuals and user guides at all-guides.com
CH01
0.000
CH02
0.000
+
UP
DOWN
+
SELECT
METER
Alarm
0.000
Ph-B
CH25
WARNING
UP
Ph-C
CH12
ALARM
0.000
UP
GENE
OVER
MCM
VOLTAGE
UP
GENE
OVER
0.000
MCM
CURRENT
UP
AUX INPUT
ALARM
UP
0000.0
METER
METER
mode
Enter Password :
* * * * * *
SELECT
DOWN
View System Info
SELECT
Find Meters
Review Meters
Setup
Communication
SELECT
Setup
Operation
SELECT
Setup
mode
DOWN
SELECT
UP
UP
UP
UP
UP
UP
UP