Checking High And Low Voltage To Ecm Motor; Checking Fan Relay Contacts-Ecm Fan Motor; Checking Relay Contacts-Psc Fan Motor; Unitary (Uc) Control Diagnostics - Goodman ComfortNet ASXC160**1AA Series Service Instructions Manual

Asxc, dsxc, and gsxc condensing units, aszc, dszc and gszc split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
ECM MOTOR
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Measure voltage between black and brown motor
leads. This should measure 208/230 volts depending
on your power supply.
2. If voltage is present proceed to check fan relay
contacts and voltage.
CHECKING FAN RELAY CONTACTS - ECM FAN MOTOR
1. Disconnect fan motor harness from plug on the UC
board.
2. Energize the system in low stage and check voltage:
• Pin 5(Blue wire) to Pin 3(Yellow wire) =
24VAC
3. Energize the system in high stage and check volt-
age:
• Pin 5(Blue wire) to Pin 3(Yellow wire) =
24VAC
• Pin 5(Blue wire) to Pin 1(White wire) = 24
VAC.
4. If voltage is present at these pins plug harness into
plug on PC board and check voltages at motor to test
for broken wires.
5. If all voltages are present motor is defective and
needs to be replaced.
CHECKING RELAY CONTACTS - PSC FAN MOTOR
50
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Disconnect the motor leads from 6-circuit fan motor wire
harness.
2. Connect a voltmeter between circuit 3 and circuits 2 (low
speed) or 1 (high speed).
NOTE: Circuit 3 is connected directly to L2.
3. Energize the system at low or high stage.
WARNING
Line Voltage now present.
4. The measured voltage between circuit 3 and circuits 2 or
1 should be approximately 0VAC, which indicates the
relay contacts are closed. A voltage measurement of
approximately 115VAC indicates the relay is open. Re-
place the control if the relay checks open when it should
be closed.

S-10A COPELAND COMFORT ALERT

UNITARY (UC) CONTROL DIAGNOSTICS

Applies to ASXC, ASZC, and DSZC 2-stage models
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
The Copeland Comfort Alert
into the unitary (UC) control. The UC control and integraged
Comfort Alert™ diagnostics provide around-the-clock moni-
toring for common electrical problems, compressor defects
and broad system faults. If a problem is detected, LED
indicators flash the proper alert codes to help you quickly
pinpoint the problem.
The diagnostic tables on following pages provide detailed
information regarding the system symptons, indicators (LED
and thermostat), potential problem(s), and corrective ac-
tions. The diagnostic information applies to systems wired
as 24VAC traditional (legacy) systems and systems wired as
communicating systems with the CTK0* communicating
thermostat.
5.0 Emergency Heat Operation
TM
-
TM
diagnostics are fully integrated