SERVICING
Troubleshooting

Motor Control Circuits

HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Turn on power to air handler or modular.
WARNING
Line Voltage now present.
2. Check voltage between pins 1 and 4 at the 4-wire motor
connector on the control board. See Electrical Checks -
Low Voltage Control Circuits section (S-16H).

Electric Heat Sequencer Outputs

HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Turn on power to air handler or modular blower.
WARNING
Line Voltage now present.
2. Disconnect the 4-circuit harness connecting the control
to the electric heater kit.
3. Provide a thermostat demand for low stage auxiliary heat
(W1). Measure the voltage between circuits 1 and 3 at
the on-board electric heat connector. Voltage should
measure 24VAC. Replace control if no voltage is present.
NOTE: Allow for any built-in time delays before making
voltage measurements. Any electric heater faults that are
present may prevent the heater output from energizing.
Verify that no heater faults are present before making
voltage measurements.
4. Provide a thermostat demand for high stage auxiliary heat
(W1 + W2). Measure the voltage between circuits 1 and
3 at the on-board electric heat connector. Measure the
voltage between circuits 2 and 3 at the on-board electric
heat connector. Voltage should measure 24VAC. Re-
place control if no voltage is present.
Communications (Applies only to Systems with Compatible
TM
ComfortNet
Outdoor Unit and CTK0*Thermostat)
The integrated air handler control has some on-board tools
that may be used to troubleshoot the network. These tools
are: red communications LED, green receive (Rx) LED, and
learn button. These are described below
a. Red communications LED – Indicates the status of the
network. Refer to the Network Troubleshooting Chart for
the LED status and the corresponding potential problem.
b. Green receive LED – Indicates network traffic. Refer to the
Network Troubleshooting Chart for the LED status and the
corresponding potential problem.
c. Learn button – Used to reset the network. Depress the
button for approximately 2 seconds to reset the network.
Voltages between the two data lines and between each data
line and common may be used to determine if the network
is operating properly.
Do the following to measure the voltages on the communi-
cations data lines.
WARNING
Line Voltage now present.
Data Line Voltage Troubleshooting and Bias
Switches
Proper data voltage is essential to robust and reliable com-
munication on the ComfortNet™ system. Any wiring issues
must be corrected for good communication.
Poor wiring connections at the terminal blocks
Low voltage wires that are shorted, grounded or
broken.
Communicating wires that are not connected to the
proper terminals at the connector.
24 volt common outside and inside are not at the
same ground potential
Bias dip switch setting conflicts between indoor
board and outdoor board.
It is STRONGLY recommended that you do not
connect multiple wires into a single terminal on the
wiring connector
Wire nuts are recommended to connect multiple
wires to connector ensuring one wire is used for each
terminal.
Failure to do so may result in intermittent operation.
Typical 18 AWG thermostat wire may be used to wire
the system components. One hundred feet is the
maximum length of wire between indoor and outdoor
units or between indoor unit and thermostat.
When outdoor transformer is used and there at least
three thermostat wires running to the outdoor unit
87