Goodman ComfortNet ASXC160**1AA Series Service Instructions Manual page 56

Asxc, dsxc, and gsxc condensing units, aszc, dszc and gszc split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
* CODE USED ON HEAT PUMP MODELS ONLY
NOTE 1: DS1, DS2 AND DS3 ARE LABELED ON THE CONTROL ABOVE EACH 7
SEGMENT LED DISPLAY
NOTE 2: 7 SEGMENT LED DISPLAY DS3 IS NOT USED
56
7 SEGMENT LED
7 SEGMENT LED
(DS2)
(DS1)
0
0
0
0
0
0
0
0
0
0
0
0
8
A
A
b
b
C
C
C
d
d
d
d
d
d
d
d
E
E
F
H
L
L
L
L
L
P
P
P
P
P
PCBHR104/PCBHR105
DESCRIPTION OF CONDITION
n
Standby
1
Low Pressure CO Trip
1
Low Side Fault
2
High Pressure CO Trip
2
High Side Fault
3
Short Cy cling
4
Locked Rotor
5
Open Circuit
6
Open Start Circuit
7
Open Run Circuit
8
No Line Voltage
9
Low Pilot Voltage
8
Pow er Up
2
Outdoor Air Temp Sensor Fault
3
Outdoor Coil Temp Sensor Fault *
0
No Indoor Airflow
9
Inadequate Airf low
3
Cool Mode Short Cycle Timer
1
Low Cool
2
High Cool
F
Def rost *
t
Max Defrost Time *
E
Forced Defrost *
0
Data not yet on Netw ork
1
Invalid Data on Netw ork
2
System Mis-Match
3
Conf iguration Mis-Match
4
Invalid Memory Card Data
E
Board Misoperation
5
Open Fus e
t
Field Test Mode
8
High Line Voltage
1
LPCO Lockout (3 Trips)
2
HPCO Lockout (3 Trips)
6
Open Start Circuit Lockout
7
Open Run Circuit Lockout
8
Low Line Voltage
3
Heat Mode Short Cycle Timer *
1
Low Heat *
2
High Heat *
0
Comp Protector Open
d
Pump Dow n
0140M00407-A