Goodman *SZC 16 SEER Technical Manual

Goodman *SZC 16 SEER Technical Manual

Goodman *szc 16 seer split system heat pumps

Advertisement

TECHNICAL MANU
TECHNICAL MANU
TECHNICAL MANU AL
TECHNICAL MANU
TECHNICAL MANU
Split System Heat Pumps
Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information.
All safety information must be followed as provided in the Service Manual.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury due to
improper service procedures or services performed by an unqualified person.
Copyright © 2009 -
*SZC 16 SEER
2010, 2012 - 2014 Goodman Manufacturing Company,
AL
AL
AL
AL
RT6214005r6
February 2014
L.P.

Advertisement

loading
Need help?

Need help?

Do you have a question about the *SZC 16 SEER and is the answer not in the manual?

Questions and answers

Summary of Contents for Goodman *SZC 16 SEER

  • Page 1 RT6214005r6 This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to February 2014 improper service procedures or services performed by an unqualified person.
  • Page 2: Product Identification

    Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Goodman will not be responsible Installation and repair of this unit WARNING WARNING...
  • Page 3 WARNING that is not design certified by damage, personal injury, or death, Goodman for use with this unit. do not store combustible materials or use gasoline or Serious property damage, personal injury, reduced unit other flammable liquids or vapors in the vicinity of this performance and/or hazardous conditions may result appliance.
  • Page 4: Product Design

    PRODUCT DESIGN Models covered by this manual come with a new 4-wire com- This unit is for outdoor installation only. Refer to figure for minimum clearances from the sides of the unit to full walls municating PCB. When paired with a compatible communi- and other objects.
  • Page 5 HEAT PUMP SPECIFICATIONS *SZC160241A*-*SZC160361A* Cooling Capacity, BTUH 24,000 24,000 36,000 36,000 Compressor R.L. Amps 10.3 11.7 16.7 15.3 L.R. Amps 52.0 58.3 82.0 83.0 Low Pressure Switch Open 22 PSIG 22 PSIG 22 PSIG 22 PSIG Close 50 PSIG 50 PSIG 50 PSIG 50 PSIG High Pressure Switch...
  • Page 6 HEAT PUMP SPECIFICATIONS *SZC160481A*-*SZC160601A* Cooling Capacity, BTUH 48,000 48,000 60,000 Compressor R.L. Amps 21.2 21.2 25.6 L.R. Amps 96.0 104.0 118.0 Low Pressure Switch Open 22 PSIG 22 PSIG 22 PSIG Close 50 PSIG 50 PSIG 50 PSIG High Pressure Switch Open 610 PSIG 610 PSIG...
  • Page 7 HEAT PUMP SPECIFICATIONS *SZC160601B* Cooling Capacity, BTUH 60,000 60,000 Compressor R.L. Amps 23.0 28.8 L.R. Amps 118.0 152.9 Low Pressure Switch Open 22 PSIG 22 PSIG Close 50 PSIG 50 PSIG High Pressure Switch Open 610 PSIG 610 PSIG Close 420 PSIG 420 PSIG Condenser Fan Motor...
  • Page 8 COOLING PERFORMANCE DATA *SZC160241A*-LOW STAGE...
  • Page 9 COOLING PERFORMANCE DATA *SZC160241A*-LOW STAGE...
  • Page 10 COOLING PERFORMANCE DATA *SZC160361A*-LOW STAGE...
  • Page 11 COOLING PERFORMANCE DATA *SZC160361A*-LOW STAGE...
  • Page 12 COOLING PERFORMANCE DATA *SZC160481A*-LOW STAGE...
  • Page 13 COOLING PERFORMANCE DATA *SZC160481A*-LOW STAGE...
  • Page 14 COOLING PERFORMANCE DATA *SZC160601A*-LOW STAGE...
  • Page 15 COOLING PERFORMANCE DATA *SZC160601A*-LOW STAGE...
  • Page 16 COOLING PERFORMANCE DATA *SZC160601B*-LOW STAGE...
  • Page 17 COOLING PERFORMANCE DATA *SZC160601B*-LOW STAGE...
  • Page 18 COOLING PERFORMANCE DATA *SZC160241A*-HIGH STAGE...
  • Page 19 COOLING PERFORMANCE DATA *SZC160241A*-HIGH STAGE...
  • Page 20 COOLING PERFORMANCE DATA *SZC160361A*-HIGH STAGE...
  • Page 21 COOLING PERFORMANCE DATA *SZC160361A*-HIGH STAGE...
  • Page 22 COOLING PERFORMANCE DATA *SZC160481A*-HIGH STAGE...
  • Page 23 COOLING PERFORMANCE DATA *SZC160481A*-HIGH STAGE...
  • Page 24 COOLING PERFORMANCE DATA *SZC160601A*-HIGH STAGE...
  • Page 25 COOLING PERFORMANCE DATA *SZC160601A*-HIGH STAGE...
  • Page 26 COOLING PERFORMANCE DATA *SZC160601B*-HIGH STAGE...
  • Page 27 COOLING PERFORMANCE DATA *SZC160601B*-HIGH STAGE...
  • Page 28: Performance Data

    PERFORMANCE DATA LOW STAGE *SZC160361A* / CA*F3743*6**+TXV / MBVC1600**-1** *SZC160241A* / CA*F3636*6**+TXV / MBVC1600**-1** Conditions: 80° IDB, 67° IWB @ 800 CFM, LOW STAGE Conditions: 80° IDB, 67° IWB @ 600 CFM, LOW STAGE Outdoor Total Sensible Latent Total Outdoor Total Sensible Latent...
  • Page 29 PERFORMANCE DATA HIGH STAGE *SZC160361A* / CA*F3743*6**+TXV/ MBVC1600**-1** *SZC160241A* / CA*F3636*6**+TXV/ MBVC1600**-1** Conditions: 80° IDB, 67° IWB @ 1200 CFM, HIGH STAGE Conditions: 80° IDB, 67° IWB @ 875 CFM, HIGH STAGE Outdoor Total Sensible Latent Total Outdoor Total Sensible Latent Total Temp.
  • Page 30 SPLIT SYSTEM HEATING PERFORMANCE *SZC160241A* EXPANDED PERFORMANCE DATA LOW STAGE MODEL: *SZC160241A* / CA*F3636*6** + TXV / MBVC1600**-1** HEATING OPERATION Outdoor Ambient Temperature 20.8 19.7 18.5 17.3 16.6 16.0 14.9 13.7 13.1 12.1 11.1 10.5 10.1 Delta T 30.2 28.6 26.9 25.2 24.1...
  • Page 31 SPLIT SYSTEM HEATING PERFORMANCE *SZC160361A* LOW STAGE EXPANDED PERFORMANCE DATA MODEL: *SZC160361A* / CA*F3743*6** + TXV / MBVC1600**-1** HEATING OPERATION Outdoor Ambient Temperature 30.3 28.7 27.0 25.3 23.4 21.7 20.0 18.1 16.7 15.4 14.5 14.0 12.6 11.1 24.1 Delta T 35.1 33.2 31.3...
  • Page 32 SPLIT SYSTEM HEATING PERFORMANCE *SZC160481A* EXPANDED PERFORMANCE DATA LOW STAGE MODEL: ASZC160481A* / CA*F4961*6** + TXV / MBE2000**-1** HEATING OPERATION Outdoor Ambient Temperature 43.2 40.9 38.5 36.0 34.4 33.3 30.9 28.5 25.7 23.7 21.8 20.6 19.9 17.8 15.8 13.8 11.8 Delta T 37.2 35.2...
  • Page 33 SPLIT SYSTEM HEATING PERFORMANCE *SZC160601A* LOW STAGE EXPANDED PERFORMANCE DATA MODEL: *SZC160601A* / CA*F4961*6** + TXV / MBVC2000**-1** HEATING OPERATION Outdoor Ambient Temperature 52.2 49.5 46.5 43.5 41.6 40.3 37.4 34.5 33.0 30.4 28.0 26.5 25.5 22.9 20.3 17.7 15.1 12.4 Delta T 40.3...
  • Page 34 SPLIT SYSTEM HEATING PERFORMANCE *SZC160601B* LOW STAGE EXPANDED PERFORMANCE DATA MODEL: *SZC160601B* CAPF4961D6 MBVC2000A - LOW STAG E HEATING OPERATION Outdoor Ambient Temperature 49.9 47.3 44.5 41.6 39.7 38.5 35.8 33.0 30.8 28.4 26.2 24.7 23.8 21.3 18.9 16.5 14.1 11.5 40.2 38.1...
  • Page 35: Heating Specifications

    HEATING SPECIFICATIONS LOW STAGE *SZC160361A*/CA*F374 3*6**+TXV/MBVC1600**-1** *SZC160241A*/CA*F363 6*6**+TXV/MBVC1600**-1** Conditions: 800 CFM Indoor Air @ 70°F DB, LOW STAGE Conditions: 600 CFM Indoor Air @ 70°F DB, LOW STAGE B asic Unit witho ut Capac ity of Unit B asic Unit witho ut Capac ity of Unit Outd oor Outd oor...
  • Page 36 HEATING SPECIFICATIONS LOW STAGE *SZC160601B* / CA*F4860*6A*+TXV/ MBVC2000**-1 Conditions:1200 CFM @ 70°F DB, LOW STAGE Basic Unit w ithout Capacity of Unit Outdoor Auxiliary Heat With KW of Auxiliary heat Am bient capacity °F. btuh c.o.p. 14.4 19.2 49.94 4.17 66.31 82.69 99.07...
  • Page 37 HEATING SPECIFICATIONS HIGH STAGE *SZC160361A*/CA*F3743*6**+TXV/ MBVC1600**-1** *SZC160241A*/CA*3636*6**+TXV/ MBVC1600**-1** Conditions: 1200 CFM Indoor Air @ 70°F DB, HIGH STAGE Conditions: 875 CFM Indoor Air @ 70°F DB, HIGH STAGE Basic U nit wit hout Cap acity of Unit Basic U nit without Capacity of Unit Outd oo r Outdoor...
  • Page 38 HEATING SPECIFICATIONS HIGH STAGE *SZC160601B* / CA*F4860*6A*+TXV/ MBVC2000**-1 Conditions:1800 CFM @ 70°F DB, HIGH STAGE Basic Unit w ithout Capacity of Unit Outdoor Auxiliary Heat With KW of Auxiliary heat Am bient capacity °F. btuh c.o.p. 14.4 19.2 71.02 4.45 87.40 103.78 120.15...
  • Page 39 PERFORMANCE DATA PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
  • Page 40: Wiring Diagrams

    WIRING DIAGRAMS *SZC160[24-60]1AA/AB HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 41 WIRING DIAGRAMS *SZC160[24-48]1AC, *SZC160601BA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.