R-410a self-contained package heat pump units

Advertisement

APH16 "M" Series with R-410A
Self-Contained Package Heat Pump Units
Installation Instructions
Our continuing commitment to quality products may mean a change in specifications without notice.
IOA-3018D
07/2021
19001 Kermier Rd. Waller, Tx 77484
www.goodmanmfg.com • www.amana-hac.com
© 2015 - 2021 Goodman Manufacturing Company, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license.
Replacement Parts..........................................................2
Safety Instructions........................................................2
General Information.......................................................2
Unit Location....................................................................3
Clearances.......................................................................4
Roof Curb Post-Installation Checks..........................5
Roof Top Duct Connections..........................................5
Rigging Details.................................................................5
Electrical Wiring............................................................6
Circulating Air And Filters...........................................8
Condensate Drain Connection......................................9
Startup, Adjustments, And Checks............................10
Air Flow Adjustments...................................................10
Heat Pump Operation.....................................................12
Maintenance...................................................................13
Appendix B Electrical Data........................................16
Appendix C Unit Dimensions.........................................17
Wiring Diagram............................................................19
Start-Up Checklist.........................................................20
Only personnel that have been trained to install, adjust,
service or repair(hereinafter, "service") the equipment
specified in this manual should service the equipment.
The manufacturer will not be responsible for any injury
or property damage arising from improper service or
service procedures. If you service this unit, you assume
responsibility for any injury or property damage which may
result. In addition, in jurisdictions that require one or more
licenses to service the equipment specified in this manual,
only licensed personnel should service the equipment.
Improper installation, adjustment, servicing or repair of
the equipment specified in this manual, or attempting to
install, adjust, service or repair the equipment specified in
this manual without proper training may result in product
damage, property damage, personal injury or death.
All rights reserved.
INDEX
WARNING
.....15

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the APH16 M Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Goodman APH16 M Series

  • Page 1: Table Of Contents

    Our continuing commitment to quality products may mean a change in specifications without notice. 19001 Kermier Rd. Waller, Tx 77484 www.goodmanmfg.com • www.amana-hac.com © 2015 - 2021 Goodman Manufacturing Company, L.P. IOA-3018D is a registered trademark of Maytag Corporation or its related companies and is used under license.
  • Page 2: Replacement Parts

    This unit must not be used as a “construction heater” HOMEOWNER SUPPORT during the finishing phases of construction on a new GOODMAN COMPANY, L.P. structure. This type of use may result in premature failure of the unit due to extremely low return air temperature 19001 KERMIER ROAD and exposure to corrosive or very dirty atmospheres.
  • Page 3: Unit Location

    EPA Regulations 4. File the claim with the following supporting Important: The United States Environmental documents: Protection Agency (EPA) has issued various a. Original Bill of Lading, certified copy, or regulations regarding the introduction and indemnity bond. disposal of refrigerants in this unit. Failure b.
  • Page 4: Clearances

    • To avoid possible illness or death of the building Full perimeter roof curbs are available from the factory occupants, do NOT locate outside air intake device and are shipped unassembled. Field assembly, squaring, (economizer, manual fresh air intake, motorized fresh leveling and mounting on the roof structure are the air intake) too close to an exhaust outlet, gas vent responsibility of the installing contractor.
  • Page 5: Roof Curb Post-Installation Checks

    Flexible duct connectors between the unit and ducts are *In situations that have multiple units, a 36” minimum recommended. Insulate and weatherproof all external clearance is required between the condenser coils. ductwork and joints as required and in accordance with Adequate clearance around the unit should be kept for local codes.
  • Page 6: Electrical Wiring

    • The distance between the crane hook and the top of Corner Weights (lb) Shipping Operating Model X (in) Y (in) the unit must not be less than 60”. Weight (lb) Weight (lb) APH1660M 33.5 27.6 • Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables.
  • Page 7 Ensure the data plate is not covered by the field-supplied CAUTION disconnect switch. • Some disconnect switches are not fused. Protect Conduit and fittings must be weather-tight to prevent the power leads at the point of distribution in water entry into the building. accordance with the unit data plate.
  • Page 8: Circulating Air And Filters

    Areas Without Convenience Outlet Low Voltage Control Wiring It is recommended that an independent 115V power source 1. A 24V thermostat must be installed for unit operation. be brought to the vicinity of the roof top unit for portable 2. Locate thermostat or remote sensor in the lights and tools used by the service mechanic.
  • Page 9: Condensate Drain Connection

    CONDENSATE DRAIN CONNECTION CAUTION Condensate Drain Connection To prevent property damage or personal injury, do not A 3/4” female NPT drain connection is supplied on the start the unit until all necessary pre-checks and tests end of the unit and bottom of the drain pan for condensate have been performed.
  • Page 10: Startup, Adjustments, And Checks

    Roof Curb Installation Check High stage airflow setting to be between 300 and 500 Inspect the roof curb for correct installation. The unit and CFM per ton, see Table below. For models with electric curb assembly should be level. Inspect the flashing of the heat the total airflow must not be less than that required roof mounting curb to the roof, especially at the corners, for for operation of the electric heaters.
  • Page 11 To confirm charge levels or, if a leak occurs and charge needs to be added to the system, it is recommended to WARNING evacuate the system and recharge refrigerant to the unit’s nameplate specifications. This unit has been rated in the HIGH VOLTAGE! cooling mode at the AHRI rated conditions of: indoor (80°F Disconnect all power before servicing or...
  • Page 12: Heat Pump Operation

    17. Make sure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. Also make sure tubes or lines are not rubbing against each other or sheet metal surfaces or edges. If so, correct the trouble.
  • Page 13: Maintenance

    Defrost Control Filters During operation the Defrost signal to the circuit board is controlled by a temperature sensor, which is clamped CAUTION to a feeder tube entering the outdoor coil. Defrost timing periods of 30,60 and 90 minutes may be selected To prevent property damage due to fire and loss of by connecting the circuit board jumper to 30, 60 and equipment efficiency or equipment damage due to dust and...
  • Page 14 Wiring Example Electric Heat Wiring Example...
  • Page 15: Appendix A Blower Performance Tables - Heat Pump

    APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP 5 Ton Heat Pump Standard Static Drive Models: APH1660M Horizontal Flow Down Flow External External Speed Static Speed Static SCFM SCFM Pressure Pressure (ESP), in w.c. (ESP), in w.c. 1299 614 0.16 1326 653 0.22 1209 674...
  • Page 16: Appendix B Electrical Data

    APPENDIX B ELECTRICAL DATA Outdoor Fan Optional Powered Optional Model Electrical Compressor Indoor Fan Motor Optional Electric Heat Power Supply Motor Convienience Power Number Rating QTY RLA LRA QTY HP FLA Type HP FLA Part # Outlet FLA Exhaust FLA 44.1/44.1 70.0/70.0 7.2/6.5 51.3/50.6 70.0/70.0...
  • Page 17: Appendix C Unit Dimensions

    APPENDIX C UNIT DIMENSIONS 73-3/8" 47-5/8" "A" 74" 48-5/16" Model Dim. "A" 5 Ton Heat Pump 43-1/2" 19-1/2 RETURN 5-5/16 11” X 25” EMBOSS DRAIN 5-7/8 THRU THRU CURB BASE LOCATION SUPPLY UTILITIES 12” X 17” 27-3/4 7-3/8 RETURN 4-1/2 11"...
  • Page 18: Appendix D Air Flow For Electric Heat

    APPENDIX D AIR FLOW FOR ELECTRIC HEAT HEATER KIT MINIMUM MAXIMUM HEATER KIT MODEL NUMBER NOMENCLATURE UNIT MODEL NUMBER SCFM SCFM 6, 7 EH*-*S05 1500 EH*-*S10 1500 APH1660M 2500 Electric EH*-*S15 1500 EH*-*S20 1550 Heater Heater Type Staged SCR (modulating) Voltage 208-230/1/60 Single phase 60 Hz...
  • Page 19: Wiring Diagram

    WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 20: Start-Up Checklist

    START-UP CHECKLIST Residential Package - (Indoor Section) Model Number Serial Number ELECTRICAL Line Voltage (Measure L1 and L2 Voltage) L1 - L2 Secondary Voltage (Measure Transformer Output Voltage) R - C Blower Amps Heat Strip 1 - Amps Heat Strip 2 - Amps BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure IN.
  • Page 21 THIS PAGE IS INTENTIONALLY LEFT BLANK...
  • Page 22 THIS PAGE IS INTENTIONALLY LEFT BLANK...
  • Page 23 THIS PAGE IS INTENTIONALLY LEFT BLANK...
  • Page 24 Our continuing commitment to quality products may mean a change in specifications without notice. 19001 Kermier Rd. Waller, Tx 77484 www.goodmanmfg.com • www.amana-hac.com © 2015 - 2021 Goodman Manufacturing Company, L.P. is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.

This manual is also suitable for:

Aph1660m

Table of Contents