Mbvc Airflow Table - Goodman ComfortNet ASXC160**1AA Series Service Instructions Manual

Asxc, dsxc, and gsxc condensing units, aszc, dszc and gszc split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
Speed Selection Dip Switches
Cool
Adjust
Selection
Selection
Switches
Switches
TAP
1
2
3
A
OFF
OFF OFF OFF
B
ON
OFF
ON
C
OFF
ON OFF
D
ON
ON
ON
Profiles
Pre-Run
A
-------
B
-------
C
-------
D
30 sec/50%
To set airflow:
(1) Select model and desired
high stage cooling airflow. Determine the cooresponding tap
( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate
ON / OFF positions. (2) Select model and installed electric
heater size. Set switches 9, 10, and 11 to the appropriate
ON/OFF positions. (3) Select the airflow adjustment factor tap
A and D are 0%; Tap B is +10%; Tap C - 10%. Set dip switches 3
and 4 to the appropriate ON / OFF positions.
To set Comfort Mode:
Select desired Comfort Mode profile
(see profiles above). Set switches 5 and 6 to the approriate
ON / OFF positions.

MBVC Airflow Table

Profile
Selection
Switches
4
5
6
OFF OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
Short-Run
OFF Delay
--------
60 sec/100%
30 sec/50%
60 sec/100%
7.5 min/82%
60 sec/100%
7. 5 min/82%
30 sec/50%
0140A00045
Htr Kw
9
10
11
MBVC1200*
3
ON
ON
ON
5
ON
ON
OFF
6
ON
OFF
ON
8
ON
OFF
OFF
10
OFF
ON
ON
15
OFF
ON
OFF
20
OFF
OFF
ON
Model
Tap
*
MBVC1200
*
MBVC1600
*
MBVC2000
MBVC16000*
MBVC2000*
600
800
600
800
635
800
740
1000
1000
1000
1400
1500
NR
NR
Low Stage
High Stage
Cool
Cool
A
400
B
540
C
670
D
800
1200
A
670
1000
B
800
C
940
D
1070
A
800
1200
B
1070
C
1200
D
1340
800
800
800
1000
1200
1500
2000
600
800
1000
1200
1400
1600
1600
1800
2000
77