Goodman ComfortNet ASXC160**1AA Series Service Instructions Manual page 61

Asxc, dsxc, and gsxc condensing units, aszc, dszc and gszc split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
Digit 3
Run time for last 4 cycles
is less than 3 minutes
each.
Compressor protector has
not tripped.
Low pressure and high
pressure switches are
closed.
Integrated control
module diagnostic/status
LED display shows the
indicated code.
Compressor and outdoor
f
.
Compressor protector trips
four consecutive times.
Average run time between
trips is less than 15
seconds.
Integrated control
module diagnostic/status
LED display shows the
indicated code.
displays error message.
Compressor and outdoor
f
or greater than
4 hours.
Low pressure and high
pressure switches are
closed.
Integrated control
module diagnostic/status
LED display shows the
indicated code.
displays error message.
Compressor and outdoor
f
.
Low pressure and high
pressure switches are
closed.
Integrated control
module diagnostic/status
LED display shows the
indicated code.
displays error message.
Digit 2
Digit 1
0
3
Short Cycling
0
4
Locked Rotor
0
5
Open Circuit
0
6
Open Start
Circuit
CMPR
03
Intermittent
SHRT
thermostat
CYCLE
demand.
Faulty
compressor
relay.
04
Compressor
ROTOR
bearings are
seized.
Failed
compressor run
capacitor.
Faulty run
capacitor wiring.
Low line voltage.
05
Power is
CIRCUIT
disconnected.
Failed
compressor
protector.
Compressor not
properly wired to
control.
06
Compressor start
START
winding is open.
Failed
compressor run
capacitor.
Faulty run
capacitor wiring.
Compressor not
properly wired to
control.
Faulty
compressor
wiring.
PCBHR104
Check thermostat
Turn power OFF prior
and thermostat
to repair.
wiring; repair/
Fault will clear after 4
replace as
consecutive normal
needed.
cycles.
Check
Fault may be cleared
compressor
by cycling 24VAC to
relay operation;
control.
replace control as
Replace with correct
needed.
replacement part(s).
Minimum compressor
runt time is changed
from 30 seconds to 3
minutes.
Check
Turn power OFF prior
compressor
to repair.
operation; repair/
Must clear fault by
replace as
cycling 24VAC to
needed.
control.
Check run
Replace with correct
capacitor; replace
replacement part(s).
as needed.
Check wiring;
repair/replace as
needed.
Verify line voltage
is within range
on rating plate;
contact local
utility is out of
range.
Check circuit
Turn power OFF prior
breakers and
to repair.
fuses.
Fault will clear after
Check wiring
normal cycle.
to unit; repair/
Fault may be cleared
replace as
by cycling 24VAC to
needed.
control.
Check
Replace with correct
compressor;
replacement part(s).
repair/replace as
needed
Check
compressor
wiring; repair/
replace as
needed.
Check
Turn power OFF prior
compressor;
to repair.
repair/replace as
Fault will clear after 1
needed.
normal cycle.
Check run
Fault may be cleared
capacitor; replace
by cycling 24VAC to
as needed.
control.
Check wiring;
Replace will correct
repair/replace as
replacement part(s).
needed.
1
61