In accordance with the N.E.C. or local codes, install a branch cir-
cuit fused disconnect near the unit. Determine wire sizes and
overcurrent protection from the unit nameplate ampacity and in
accordance with the Minimum Filter Size or the N.E.C. The wiring
should never be sized smaller than is recommended by either of
these two sources.
Fuses smaller than that recommended on the rating plate could
result in unnecessary fuse failure or service calls. The use of
protective devices of larger size than indicated could result in ex-
tensive damage to the equipment. The manufacturer bears no
responsibility for damage caused to equipment as result of the
use of larger than is recommended size protective devices.
All units have undergone a run test prior to packaging for ship-
ment. This equipment has been started at minimum rated voltage
and checked for satisfactory operation. Do not attempt to operate
this unit if the voltage is not within the minimum and maximum
voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit.
The unit must be permanently grounded in accordance with local
codes, or in absence of local codes, with N.E.C ANSI/ NFPA NO.
70-1984 or latest edition by using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where codes
permit.
FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT
CONTACTOR
24 VOLT CONTROL WIRING
*NOTE: LOW VOLTAGE CONNECTORS do not apply to heat pumps with
electric heat.
IMPORTANT NOTE: Some single phase units are equipped with a
single-pole contactor. Exercise caution when servicing as only one
leg of the power supply is broken with the contractor.
To wire the unit, make the following high and low voltage connec-
tions.
HIGH VOLTAGE
!
D
ALL
ISCONNECT
POWER BEFORE SERVICING OR INSTALLING
M
THIS UNIT.
ULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.
H
V
W
IGH
OLTAGE
IRING
Single Phase- Two leads should be connected to terminals
L1 & L2 in the electrical control section, using wire sizes
specified in wiring table.
L
V
W
OW
OLTAGE
IRING
Heat Pumps- Connect 24V wires from the thermostat to
the corresponding wires in the control box using No. 18
AWG as follows:
G R W
R
G
WARNING
GPH15
Terminal
Red
Green
Orange
White
Brown
Purple
Yellow
Thermostats must be set to energize "G" during cooling.
This is default on most all thermostats.
GPH1542 - GPH1560 have 2-stage cooling and require
*Optional field installed heat connections
I
W
NTERNAL
IRING
A diagram detailing the internal wiring of this unit is located on the
electrical box cover. If any of the original wire supplied with the
appliance must be replaced, the wire gauge and insulation must
be the same as the original wiring.
Transformer is wired for 230 volts on the 208/230 models. See
See
wiring diagram for 208 volt wiring.
*NOTE
1. For branch circuit wiring (main power supply to unit
disconnect), the minimum wire size for the length of run
can be determined using the circuit ampacity found on the
unit rating plate and the table below. From the unit
disconnect to unit, the smallest wire size allowable may be
W
used for the ampacity, as the Disconnect must be in sight
of the unit.
BRANCH CIRCUIT AMPACITY 15 20 25 30 35 40 45 50
SUPPLY WIRE LENGTH -
2. Wire size based on 60° C rated wire insulation and 30° C
Ambient Temperature (86° F).
3. For more than 3 conductors in a raceway or cable, see the
N.E.C. for derating the ampacity of each conductor.
STARTUP, ADJUSTMENTS, AND CHECKS
HIGH VOLTAGE
D
ISCONNECT
M
THIS UNIT.
ULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.
7
24 - 36
Thermostat
R (24V)
G (fan)
O (rev. valve)
nd
W1 (heat, 2
)
rd
W2 (heat, 3
)
Not used
Y (cool)
2-stage heat/cool with optional
third stage electric heat thermostat.
FEET
200
6
4
150
8
6
100
10
8
50
14 12 10 10
WARNING
!
ALL
POWER BEFORE SERVICING OR INSTALLING
42 - 60
Thermostat
R (24V)
G (fan)
O (rev. valve)
nd
W1 (heat. 2
)*
rd
W2 (heat, 3
)*
Y1 (Low cool)
Y2 (Hi cool)
4
4
3
3
2
2
6
4
4
4
3
3
8
6
6
6
4
4
8
8
6
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gph1530m41Gph1548m41Gph1542m41Gph1560m41Gph1536m41

Table of Contents