3-3 Monitoring the Temperature of an Industrial Furnace (K3MA-L)
•
The input type is set to 16 (R element).
•
The unit of temperature is set to "°C".
•
Comparative output 1 is used as outside-the-range signal action, and the OUT
upper-limit value is set to "1000°C" and the OUT lower-limit value is set to
"800°C".
Level
Parameter
in-t
Initial setting
d-u
out1.t
Operation
out1.h
setting
out1.l
For details of parameters, refer to "CHAPTER 5 OPERATION".
When the internal temperature reaches 1000 °C or lower than 800 °C, compara-
•
tive output 1 is turned ON.
Set value
16
c
hi-lo
1000
800