Parameter Setting
Operation
3-2 Monitoring the Internal Pressure of a Tank (K3MA-J)
The scaling is set as follows.
INP1: 4.00
DSP1: 0
INP2: 20.00
DSP2: 9800
Position of decimal point: \\\\.\
Comparative output 1 is used to generate an upper-limit signal action and the
OUT upper-limit value is set to "550.0 kPa".
Comparative output 2 is used to generate a lower-limit signal action and the OUT
lower-limit value is set to "100.0 kPa".
Level
Parameter
in-t
inp.1
dsp.1
inp.2
Initial setting
dsp.2
dp
out1.t
out2.t
out1
Operation
setting
out2
For details of parameters, refer to "CHAPTER 5 OPERATION".
When the internal pressure of the tank reaches 550.0 kPa, comparative output 1
is turned ON.
When the internal pressure decreases to 100.0 kPa, comparative output 2 is
turned ON.
Set value
4-20
4.00
0
20.00
9800
\\\\.\
hi
lo
550.0
100.0
3-5