Long Cable Filters

For GenIV, output filters are typically required when cable lengths on the output of the drive
exceed 7500 feet. At this distance and beyond, the effective switching frequency harmonics
and sidebands may excite a cable resonance, resulting in transmission line over-voltages at
the motor terminals. The output L-C filter decouples the drive output from the cable/motor
dynamics. NXG II control supports output filters for all control modes; however, torque
responses and high starting torque capabilities are somewhat diminished due to the added
components. The filter capacitor currents are monitored by NXG II control through the SCB,
and active damping is provided in lieu of additional hardware resistors.
Note
GenIV drives should not operate into the O-M region when output filters are required.
Therefore, nine cell system is limited to an output voltage of 4005 V. Twenty-four cell
systems are limited to 10000 V.
5.4.1

Reactors and Capacitors

When the GenIV requires an OUTPUT FILTER, the drive output is equipped with an output
inductor and capacitor filter. These components cannot be packaged into the core
configuration due to space limitations; therefore, they are housed in transition cabinets.
Tables "Nine Cell OutputFilter, Capacitance" and "Nine Cell Output Filter, Inductance" list the
required inductance and capacitance for GenIV output L-C filters.
The reactors are typically custom engineered, and may include an overload rating that
matches the cell type and two sets of thermal protectors embedded into the windings.
The capacitors are heavy duty IEEE Standard 18 rated. Most commonly, available off-the-
shelf capacitors are rated for 60 Hz.
The filter connects to the output of the motor drive's T1, T2, and T3 connections. The long
cable load is then connected to the load side of the filter reactors. The filter may include a
customer-supplied down hole monitoring system (DHMS). Special attention is required and
small resistors may need to be placed in series with the DHMS to prevent fuse failures
during motor starting. The filter components are sized, based upon the continuous current
rating of the power cells and maximum voltage available (without O-M) of the drive.
Table 5- 21
Nine Cell Output Filter, Capacitance
Cell Size
ZFL @ 4005 V
40 A
57.81 Ohms
70 A
33.03 Ohms
100 A
23.12 Ohms
140 A
16.52 Ohms
200 A
11.56 Ohms
260 A
8.89 Ohms
Product User Manual
Operating Instructions, Version AE 12/2009, A5E01454341C
Q, Reactive
@ 60 Hz, 4160 V, 3 Ph
25 kVAr
50 kVAr
75 kVAr
100 kVAr
150 kVAr
200 kVAr
C, Capacitance
@ 50 Hz
3.83 μF
7.66 μF
11.5 μF
15.32 μF
22.99 uF
30.65 uF
Product Description
5.4 Long Cable Filters
C %
C %
@ 60 Hz
6.95
8.35
7.95
9.54
8.35
10.00
7.95
9.54
8.35
10.02
8.56
10.28
97