The transformers are sized on a 1000 VA per Hp basis (as shown in Chapter 1, and further
shown below); however, other factors must be considered, such as motor lead length, motor
service factor, environment ambient and altitude, and power cell redundancy (N+1 3300 V
project). These factors may increase the kVA size of the Perfect Harmony transformer as
follows:
Table 5- 6
1. Transformer initial sizing is based upon 1000 VA per Hp (including motor service
2. If ambient temperature exceeds 45°C, then transformer size is increased by:
3. If altitude exceeds 3300 feet above sea level, then transformer size is increased by:
68
GenIV Transformer Sizing and Derating Factors1*,2*
factor):
kVA
= Hp * Service Factor
1
kVA
= kVA
* [175/(220-AMB)]^0.5
2
1
kVA
= kVA
* [1+0.00003*(ALT-3300)]
3
2
Operating Instructions, Version AE 12/2009, A5E01454341C