Panasonic AFP7CPS Series User Manual page 29

Communication cassette ethernet type fp7-series, cpu unit, extension cassettes ethernet x 1ch type
Table of Contents

Advertisement

 Communication Settings
Parameters
Protocol Mode
Action Mode
Communication Mode
Send type
Source Port
No.
Server
Setting
(Note1)
Timeout
Destination
IP Address
Destination
Port No.
Client
Source Port
Setting
No.
(Note2)
Timeout
(Note1): This parameter is valid, if "Server Mode" is selected.
(Note2): This parameter is valid, if "Client Mode" is selected.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Protocol Mode of Communication cassette AFP7 CCET1
Select TCP or UDP.
Action Mode of Communication cassette AFP7 CCET1
Select Client Mode or Server Mode.
Communication Mode of Communication cassette AFP7
CCET1.
Select MEWTOCOL or General communication to match
the communication mode setting of FPWINGR7.
Method for transmitting data to partner devices.
Select UNICAST or BROADCAST.
It is valid when selecting UDP in the communication
protocol.
Port number that AFP7 CCET1 opens.
Range: 502 to 32767
If AFP7 CCET not communicate with a destination device
during this setting time (seconds) in the state that
connection is established, connection will be cut.
Range:0 to 1800s
When 0 is set, the connection will not be cut.
Specify IP address of destination
Set an IP address other than 0.0.0.0 and 255.255.255.255.
Specify port number of destination
Range: 502 to 32767
Source port number of a destination device
Range: 0, 1025 to 32767
When 0 is set, optional.
If AFPX-COM5 not communicate with a destination device
during this setting time (seconds) in the state that
connection is established, connection will be cut.
Range: 0 to 1800 s
When 0 is set, the connection will not be cut.
4.2 Specified using Configurator WD
Default
TCP
Server Mode
MEWTOCOL
UNICAST
9095
15
192.168.1.100
9094
9095
15

Advertisement