Service; List Of Error Numbers - Siemens SITRANS F C MASSFLO MASS 6000 Ex-d Manual

Sitrans f c massflo series mass flowmeters signal converter type mass 6000 ex-d sensor type mass 2100 compact or remote mounted
Table of Contents

Advertisement

SITRANS F C MASSFLO
6.

Service

6.1 List of error numbers

    
6. Service
Error
Error text
No.
Remedy text
1
I1 - Power on
OK
2
I2 - Add-on module
Applied
3
I3 - Add-on module
Install
4
I4 - Param. corrected
OK
20
W20 - Totalizer 1
Reset manually
20
W20 - Totalizer 2
Reset manually
21
W21 - Pulse overflow
Adjust pulse settings
W22 - Batch timeout
22
Check installation
23
W23 - Batch overrun
Check installation
24
W24 - Batch neg. flow
Check flow direction
30
W30 - Flowsaturated
Adjust max. flow
31
W31- Empty pipe
32
W32 - Temp. to high
Adjust temperature
33
W33 - Temp. to low
Adjust temperature
34
W34 - Zero Adj. fail
Check flow = zero
35
W35 - Current Out 1
Check max. settings
W36 - Freq/Pulse Out1
36
Check max. settings
40
P40 - SENSORPROM
Insert
41
P41 - Parameter range
Switch off and on
42
P42 - Current output
Check cables
43
P43 - Internal error
Switch off and on
49
P49 - Protec. viol.
Switch off and on
50
P50 - Temp. cable
Check cable
51
P51 - Pick-up 1
Check cable/install.
52
P52 - Pick-up 2
Check cable/install.
60
F60 - CAN comm. error
Converter/add-on module
61
F61 - SENSORPROM
Replace
F62 - SENSORPROM
62
Replace
63
F63 - SENSORPROM
Replace
70
F70 - Pick-up phase
F71 - Driver phase
71
80-83
F80, 81, 82, 83 - Internal error Restart or replace
84
F84 - Sensor level
97
F97 - Add-on module to old
Error code level:
W = Warning, F = Fatal, P = Permanent
SFIDK.PS.028.Q1.02
#Comment
Power on has activated
A new module has been added to the system
An add-on module is defect or has been removed.
This can also be an internal add-on module
A less vital parameter in the converter has been re-
placed by its default value
During initialisation the check of the saved totalize
value has failed. It is not possible to rely on the
saved totalizer value any more. The totalizer value
must be reset manually in order to rely on future
readings
During initialisation the check of the saved totalize
value has failed. It is not possible to rely on the
saved totalizer value any more. The totalizer value
must be reset manually in order to rely on future
readings
Actual flow is too big compared with pulse width and
mass/pulse
Duration of batching has exceeded a predefined
max. time
Batch quantity has exceeded a predefined maximum
overrun mass or volume
Negative flow direction during batch
Flow is above Q
settings
max.
Pipe is empty
The temperature of the fluid has exceeded the max.
temperature rating of the sensor (180 °C)
The temperature of the fluid has exceeded the min.
temperature rating of the sensor (-50 °C)
The zero-point adjustment values are outside the limit
because there is not zero flow in the sensor. Check
zeroflow conditions, valves, pumps etc.
Current output exceeds 120%. Ensure that the sensor is
correctly sized and check max. flow setting
Freq/Pulse output exceeds 120%. Ensure that the sensor
is correctly sized and check max. flow setting
    
SENSORPROM
unit not installed
A parameter is out of range.
The error will disappear at the next power-on
Current loop is disconnected or the loop resistance
is too big
Internal error
Too many errors occured at the same time.
Some errors are not detected correctly
Error in temperature sensor, check cables and
connectors
Pick-up 1 amplitude too low. Check cables or application
for damping (air/gas in liquid)
Pick-up 2 amplitude too low. Check cables or application
for damping (air/gas in liquid)
CAN bus communication error. An add-on module, the
display module or the converter is defect
    
err.
It is not possible to rely on the data in SENSOR-
PROM
unit
    
ID
The SENSORPROM
product ID. The SENSORPROM
type of product SITRANS F C MASSFLO,
SITRANS F US SONOFLO etc.
    
It is not possible to read from the SENSORPROM
unit
Check cables/polarity
Check cables/polarity
Pick-up amplitud saturated
Replace
unit ID do not comply with the
unit is from another
Outputs
Input
status
status
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Reduced
pulse width
Active
Batch out-
put on zero
Active
Batch out-
put on zero
Active
Active
Active
Max. 120 %
Active
Zero
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Zero
Inactive
Active
Active
Zero
Inactive
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
25