Testing Detectors - Siemens OOH740-A9-Ex Technical Manual

Automatic fire detector
Hide thumbs Also See for OOH740-A9-Ex:
Table of Contents

Advertisement

7.2 Testing detectors

Building Technologies
Fire Safety
WARNING
Use of testers in potentially explosive atmospheres
Risk of explosion
Testers RE6 and RE7T must only be operated in the area not at risk.
Testing of the point detector OOH740-A9-Ex can be carried out with one or more of
the following tools:
Detector tester RE6
l
Test gas
l
REF8-S (recommended)
REF8
Hot air
l
Detector tester RE7T for heat detectors
The table below shows suitable tools for testing the different sensor modes of the
point detector:
Sensor mode
Sensor mode 0
Sensor mode 1
Sensor mode 2
X = suitable
– = not suitable
The fire detectors are highly resistant to deceptive phenomena. This means that
optical fire detectors, for example, will recognize the immediate occurrence of
smoke (such as that which occurs during testing with test gas) as a deceptive
phenomenon and will not trigger an alarm. This is desirable in normal operation;
however, it does make testing with test gas problematical.
To enable detector testing with test gas or hot air, the detector must be switched to
test mode. Testing with test gas or hot air differs with addressed and collective
detector lines.
Addressed detector lines (C-NET)
On addressed detector lines, the detector or detector zone can be switched to
'Test' mode on the control panel. Testing with test gas or hot air is then possible
without problems.
Collective detector lines
Detectors on a collective line are automatically switched to test mode for 3 minutes
during startup and reset. A detector that has been newly inserted (or that has been
briefly removed from the detector line and re-inserted) is therefore automatically in
test mode during the first 3 minutes.
To trigger a detector using test gas, normally 2...4 gas discharges at intervals of
approx. 2 seconds are required. When the detector is in test mode, activation
takes place after approximately 10 seconds.
Maintenance / Repair
7
Testing detectors
Test gas
Hot air
X
X
X
X
A6V10367521_h_en_--
2015-02-02
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents