Testing Detectors - Siemens FDOOT241-9 Technical Manual

Automatic fire detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

7.3

Testing detectors

Building Technologies
Fire Safety & Security Products
Depending on the detector, testing may be performed with one or more of the
following accessories:
Detector exchanger and tester FDUD29x (recommended)
Test gas
‒ REF 8-S (recommended)
‒ REF 8
Hot air fan
The following table shows which detectors may be tested with which test aids.
Detector
FDOOT241-9/-8 (sensor mode 0)
FDOOT241-9/-8 (sensor mode 1)
FDOOT241-9/-8 (sensor mode 2)
FDOOT221
FDO2x1
FDT2x1
Depending on the detector, the following must be taken into account:
Detector in
To be considered
test mode
FDOOT
The FDOOT with ES < 13 reveals the same optical and thermal
sensitivity level in all parameter sets.
From ES 13, the detector reacts in correspondence with the
parameter set in test mode. This means when the neural fire detector
is operated as a heat detector (sensor mode 1), it must be thermally
checked as well.
FDO
The detector reacts optically with medium sensitivity (2 %/m).
FDT
The detector reacts when a temperature of 60 °C is reached or at a
temperature increase of 22 K/min.
When the detector is in alarm condition, the internal alarm indicator flashes
brightly every second.
Detector
Test gas
exchanger and
tester
X
X
X
X
X
X
X
X
X
X
Maintenance / repair
Hot air fan
X
X
X
X
81
007004_k_en_--
16.04.2009

Hide quick links:

Advertisement

Table of Contents