Specification - Siemens OOH740-A9-Ex Technical Manual

Automatic fire detector
Hide thumbs Also See for OOH740-A9-Ex:
Table of Contents

Advertisement

4.3.2.2
No.
Name
1
A1R
60 °C rate of rise
2
BR
80 °C rate of rise
3
A1S
60 °C maximum
4
BS
80 ℃ Maximum
14
Application-specific parameter sets
15
Building Technologies
Fire Safety

Specification

Operating temperature
Static activation
typ. / max.
temperature
[°C]
[°C]
25 / 50
60
40 / 65
80
25 / 50
60
40 / 65
80
Applicable with slow temperature increases <1 K/min.
1
Applicable with fast temperature increases of >10 K/min. When there is a slow
2
temperature increase of <10 K/min, this value rises by a few degrees.
All parameter sets apart from 14 and 15 comply with standard EN 54-5.
Parameter sets for addressed operation
Differential activation
temperature
1
2
∆T [K]
25
29
Planning
4
Differential activation
possible from:
[°C]
3
30
39