4
Planning
Parameter sets for addressed operation
4.3.1.2
No. Name
Risk of injury to
persons
small ...
large
8
High
Suppression
5
Suppression
0
High
and
Compensation
7
2
Robust
4
Balanced
6
Fast Response
9
High Sensitive
Fast
36
Building Technologies
Fire Safety
High Sensitive Fast (9):
This parameter set is suited for applications requiring very high sensitivity levels. It
reveals a significantly higher optical and thermal sensitivity than 'Fast Response'.
This parameter set is also suited for applications that can otherwise only be
covered with special detectors.
Download 1 (14) / download 2 (15):
Application-specific parameter sets that can be loaded on site (depending on the
control panel).

Use

Concentration
of valuable
items
low ...
high
The 'High Suppression' and 'High Sensitive Fast' parameter sets are only suited
for special applications.
Room
Deceptive
geometry
phenomena
simple ...
few ...
complex
many
Risk of fire
Critical fire size
small ...
small ...
large
medium
A6V10367521_h_en_--
2015-02-02