Control; Weather-Compensated Control; Room Temperature-Compensated Control - Siemens RVD110 Basic Documentation

District heating and domestic hot water controllers
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
/ /
T
T
Rx
/
1
2
E
Generation of setpoint with weather-compensated control with room temperature influence
*
Multiplier
E
Room authority
H
Heating curve
L
Limiter
S
Heating curve slope
T
Composite outside temperature
AM
T
Room temperature setpoint
Rw
T
Room temperature
Rx
T
Flow temperature setpoint
Vw
11.5

Control

11.5.1 Weather-compensated control

Prerequisites for this type of control:
• Outside sensor connected
• No room unit connected or, if connected, room authority set to 0 (minimum)
The compensating variable for weather-compensated control is the composite outside
temperature. The assignment of the flow temperature setpoint to the compensating
variable is made via the set heating curve. In that case, the room temperature will not
be taken into consideration.
Main application of this type of control are plants or buildings in which
• several rooms are occupied at the same time
• none of the rooms is suited as a reference room for the room temperature

11.5.2 Room temperature-compensated control

.
Prerequisites for this type of control:
• Room unit connected
• No outside sensor connected
If no outside sensor is connected, the setting on operating line 70 (room temperature
influence) is inactive.
The compensating variable for room temperature-compensated control is the deviation
of the actual room temperature from the setpoint from which the room authority is gen-
erated. In addition, an assumed outside temperature of 0 °C is used for generating the
setpoint.
• When there is no room temperature deviation, the controller maintains the flow tem-
perature setpoint generated by the heating curve slope at an outside temperature of
0 °C
Basic Documentation RVD110, RVD130
11 Function block Space heating
Rw
s
+50 K
L
-50 K
Operating line 5 = setting of heating curve slope
Operating line 69 = setting of heat gains
Operating line 70 = setting of room temperature influence (gain factor)
Operating line 71 = parallel displacement of heating curve
T
AM
s
1
s
H
T
Vw
37/94
CE1P2381E
27.05.2004