Function Block End-User D.h.w. Heating; Operating Lines; Program; Setpoint Adjustments - Siemens RVD110 Basic Documentation

District heating and domestic hot water controllers
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
7
Function block End-user d.h.w. heat-
ing
7.1

Operating lines

Line
Function, parameter
17
Weekday for entering the d.h.w. program
18
Release period 1 start
19
Release period 1 end
20
Release period 2 start
21
Release period 2 end
22
Release period 3 start
23
Release period 3 end
41
D.h.w. normal setpoint
42
D.h.w reduced setpoint
Setting --:-- means: Release period is inactive
7.2
D.h.w. program
The d.h.w. program of the RVD110 / RVD130 affords 3 release periods per day. Also,
every weekday can have different release periods. Each release period is defined by a
start and an end time.
When entering "1-7" on operating line 17, the d.h.w. program applies to all weekdays.
The entry can be simplified as follows: If the times for the weekend differ from those for
the other weekdays, first enter the times for the entire week and then change weekdays
6 and 7 as required.
The settings are sorted and overlapping release periods combined.
When setting --:-- for the start or the end, the release period will be negated.
However, the release of d.h.w. heating can also take place according to other pro-
grams. The selection is made on operating line 101.
7.3

Setpoint adjustments

• The nominal d.h.w. setpoint is to be set on operating line 41. Its setting range de-
pends on the type of plant (for details, refer to section 16.5 "Maximum setpoint".
• The reduced d.h.w. setpoint can be adjusted on operating line 42 between 8 °C and
the nominal setpoint. In connection with the d.h.w. program, it takes effect between
the release phases (refer to the above section 7.2).
w
BW
Nom
Red
06:00
Nom Nominal setpoint
Red
Reduced setpoint
t
Time
w
D.h.w. setpoint
BW
Basic Documentation RVD110, RVD130

7 Function block End-user d.h.w. heating

Unit
hh:min
hh:min
hh:min
hh:min
hh:min
hh:min
°C
°C
08:00
11:30
13:30
Factory setting
Range
Current weekday
1...7, 1-7
06:00
00:00...24:00
22:00
00:00...24:00
--:--
00:00...24:00
--:--
00:00...24:00
--:--
00:00...24:00
--:--
00:00...24:00
55
variable
40
8...normal setpoint
t
16:00
CE1P2381E
27/94
27.05.2004