Function Block Standard Values And Fault Indication; Operating Lines; Reset End-User Level; Display Of Faults - Siemens RVD110 Basic Documentation

District heating and domestic hot water controllers
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
9
Function block Standard values and
fault indication
9.1

Operating lines

Line
Function, parameter
49
Reset of operating lines 2...23 (end-user level)
50

Display of faults

9.2

Reset end-user level

If operating line 49 is set to 1, all the current settings on the end-user level (operating
lines 2...23) will be cleared. In that case, the factory settings will be used again.
Proceed as follows:
1. Select operating line 49.
2. Keep buttons
and
display is the normal status.
3. If 1 appears, the controller has retrieved the factory settings.
9.3
Display of faults
Faults in the measuring circuits detected by the controller appear on the display as
(error) as well as on operating line 50, accompanied by an error code:
Error code Cause
10
Fault outside sensor
30
Fault flow temperature sensor
40
Fault return temperature sensor on the primary side
42
Fault return temperature sensor on the secondary side
50
Fault d.h.w. temperature sensor
61
Fault room unit
62
Device with wrong PPS identification connected
86
Short-circuit on the room unit bus (PPS)
Basic Documentation RVD110, RVD130

9 Function block Standard values and fault indication

Unit
depressed until the display changes. A flashing 0 on the
Factory setting
Range
0
0 / 1
Display function
CE1P2381E
27.05.2004
Er
29/94

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rvd130

Table of Contents